PMCS Interface Toolkit
Each "Alarm indicator" as defined by the Event Logger will appear to CIMPLICITY
as a DDE Integer item which can have the following values/states:
State
Normal (no alarm)
Alarm Active - Unacknowledged
Alarm Active - Acknowledged
Alarm Reset - Unacknowledged
(alarm occurred but later went off before being
acknowledged)
Alarm Disabled
(Event Logger has disabled this alarm indicator)
Each panel button displays one of five different colors, based on the states defined
above. A fill color animation link controlled by an indirect integer tag is used to
change colors. The fill color link is set as follows:
<= 9: Dark Grey
10 -> 19: Grey
20-> 29: Grey (will also have a flashing Red animation link)
30 -> 39: Red
>= 40: Yellow
Tag
Value
10 - 19
20 - 29
30 - 39
40 - 49
0
Configuring and Using PMCS Wizards
Default
Color
Solid Gray
Red Blinking
Solid Red
Solid Yellow
Dark Gray
45