Honeywell Manning GM-1 Instruction And Installation Manual page 9

Gas monitoring alarm system
Table of Contents

Advertisement

2
Installation
Figure 2: Wiring diagram for the Manning GM-1 Gas Monitoring Alarm System
TP
GND
7
1
L
N
120 VAC
MODEL G/M
MAINBOARD REV D
*Relay rating 3 amp. User must fuse to protect.
Note: Green wire earth ground must be connected to grounding
stud marked
Bare wrap— to "SHLD" terminal of sensor
Black— to "GND" terminal of sensor
Red— to "+24" terminal of sensor
White— to "SIG" terminal of sensor
Manning GM-1 Gas Monitoring Alarm System
continued
WARNING
ALARM
TP
ADJUST
ADJUST
+20V
TP
WARNING
WARNING
RELAY
6
FUSE RATING
250V 1.0 AMP
NO
C
NC
NO
C
WARNING
ALARM
RELAY*
RELAY*
19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.
BOT TOP
TP
TP
ALARM
SIG
ALARM
RELAY
C11
+
+
+ 24
SHLD GND
NC
NO
C
NC
FAULT
RELAY*
FAULT
RELAY
+
SIG
Risk of electrical shock.
Potential hazard.
9