Operation
Maintenance
G
The Manning GM-1 is designed for long life and high
reliability. Honeywell Analytics recommends
checking signal voltages monthly and logging them
on the data sheet included with your Manning GM-1.
Additionally, the sensor being monitored should be
exposed to the target gas on a monthly basis while
all alarm functions are verified at the Manning GM-1.
This will test the sensor and any equipment con-
nected to the relays in addition to the Manning GM-1.
Figure 4: Troubleshooting the Manning GM-1 Gas Monitoring Alarm System
Display power
supply voltage
+20V
VDC
Black
Red
-
+
0.4 - 2.0 V
VDC
Black
Red
-
+
Signal from sensor
Risk of electrical shock.
Manning GM-1 Gas Monitoring Alarm System
continued
WARNING
ADJUST
TP
TP
GND
+20V
7
TP
WARNING
WARNING
AC fuse
1
6
FUSE RATING
250V 1.0 AMP
L
N
NO
C
NC
120 VAC
WARNING
RELAY*
MODEL G/M
MAINBOARD REV D
Potential hazard.
19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved.

Replacement Parts

H
For replacement parts, contact Honeywell Analytics.
Be sure to give serial number and model number of
unit.
ALARM
ADJUST
BOT TOP
TP
TP
ALARM
SIG
ALARM
RELAY
RELAY
C11
+
+
SHLD GND
NO
C
NC
NO
C
NC
ALARM
FAULT
RELAY*
RELAY*
Sensor current draw
(1mV per 10 mA)
SENSOR DEPENDENT
mVDC
Black
-
FAULT
RELAY
+
+ 24
SIG
Black
-
Power supply
voltage to sensor
Red
+
+24V
VDC
Red
+
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents