7.2 Troubleshooting

The table below shows the trouble and its remedy.
Trouble
Input type
setting error
Analog signal
wire breakage
(4-20mA only)
Analog signal
limit over
MPU error
ROM error
DP-RAM error Bit C is ON
External 24V
error
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Module
LED
status info
Bit 7 is ON
ON
(if the error
occurs in all
channels, it
is OFF)
Bit 8 is ON
ON
Bit 9 is ON
ON
Bit A is ON
OFF
Bit B is ON
OFF
OFF
Bit E is ON
OFF
Module operation
The error channel
Invalid input type
stops the
parameter was set.
conversion. The A/D
conversion data is 0.
The A/D conversion
In the 4-20mA
data of the channel
input, less than
is 0.
4mA signal is input.
The A/D conversion
Analog input signal
data of the channel
is out of the range.
is limited by the limit
value.
The A/D conversion
Internal processor
is stopped.
operation is not
normal.
The A/D conversion
EEPROM data
is stopped.
error is detected.
The A/D conversion
Buffer memory
is stopped.
access error is
occurred.
The A/D conversion
Internal 15V
is stopped.
voltage is not
normal.
7. Troubleshooting
Cause
Remedy
Set the correct
input type
parameter.
Check the analog
signal wire.
Check the signal
source (sensor).
Execute reset
command, or
cycle power off
and on.
Cycle power off
and on.
Cycle power off
and on.
Check the
external 24Vdc
power supply.
User's Manual