Toshiba AD268 User Manual page 77

Programmable controller prosec t2-series analog i/o modules
Table of Contents

Advertisement

PART 3 TC218
6. Parameters
The TC218 has the memory that stores the control parameters, input type designation, module
status information, etc. This memory is called the buffer memory. To access (read/write) this
memory from the T2 program, READ and WRITE instructions are used.
6.1 Memory map
The contents of the TC218's buffer memory are as follows.
Address
H8000
H8001
H8002
H8003
H8004
H8005
H8006
H8007
H8008
H8009
H800A
H800B
H800C
H800D
H800E
H800F
H8010
H8011
H8012
H8013
H8014
H8015
H8016
H8017
H8018
H8019
H801A
H801B
H801C
H801D
H801E
H801F
H8020
H8021
H8022
:
H8027
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Contents
F
Gain calibration value for channel 1
Gain calibration value for channel 2
Gain calibration value for channel 3
Gain calibration value for channel 4
Gain calibration value for channel 5
Gain calibration value for channel 6
Gain calibration value for channel 7
Gain calibration value for channel 8
Offset calibration value for channel 1
Offset calibration value for channel 2
Offset calibration value for channel 3
Offset calibration value for channel 4
Offset calibration value for channel 5
Offset calibration value for channel 6
Offset calibration value for channel 7
Offset calibration value for channel 8
Averaging times for channel 1
Averaging times for channel 2
Averaging times for channel 3
Averaging times for channel 4
Averaging times for channel 5
Averaging times for channel 6
Averaging times for channel 7
Averaging times for channel 8
Input type setting for channel 1
Input type setting for channel 2
Input type setting for channel 3
Input type setting for channel 4
Input type setting for channel 5
Input type setting for channel 6
Input type setting for channel 7
Input type setting for channel 8
Command register
Response register
No use
0
Use WRITE instruction to write
data into these addresses.
Use READ instruction to read
data from this address.
6. Parameters