General System and Facility Guidelines

Electrical Load Requirements (Circuit Breaker Sizing)

Electrical Load Requirements (Circuit Breaker Sizing)
Appendix A summarizes electrical power load (KVA input) requirements for this HP server but additional
capacity should be added for equipment upgrading or expansion.
It is good practice to derate power distribution systems for one or more of the following reasons:
To avoid nuisance tripping from load shifts or power transients, circuit protection devices should never be
run above 80% of their DC current ratings.
Safety agencies derate most power connectors to 80% of their DC current ratings.

Power Quality

HP equipment is designed to operate over a wide range of voltages. However, damage can occur if this range is
exceeded. Severe electrical disturbances can exceed the design specifications of the equipment.

Sources of Voltage Fluctuations

Voltage fluctuations, sometimes called glitches, affect the quality of electrical power. Common sources of these
fluctuations are:
Fluctuations occurring within the facility's distribution system
Utility service low-voltage conditions (such as sags or brownouts)
Wide and rapid variations in input power frequency
Electrical storms
Large inductive sources (such as motors and welders)
Faults in the distribution system wiring (such as loose connections)
Microwave, radar, radio, or cell phone transmissions

Power System Protection

Computer systems can be protected from the sources of many of these electrical disturbances by using:
A dedicated power distribution system
Power conditioning equipment
Over- and under-voltage detection and protection circuits
Screening to cancel out the effects of undesirable transmissions
Lightning arresters on power cables to protect equipment against electrical storms