17.0 GAS PRESSURE CHECK

The heater regulator controls the burner pressure which should be
checked at the pressure test point located on the appliance inlet pipe .
The appliance inlet pipe runs between the regulator and the gas valve
and the test point is located next to the regulator as shown in Figure 7a .
Turn off the gas supply before removing the pressure
test point screw.
The test point is situated before the appliance gas valve so it will be
necessary to turn off the gas supply before removing the test point
screw . Connect the pressure gauge .
Figure 7a - Remove test point screw
Turn on the gas supply and light the heater . Turn the control to the high
flame setting and check the pressure . The pressure regulator on manual
models is preset and locked to avoid tampering . If the pressure is not as
specified in Table 1 on Page 7, replace the regulator with P/N H6063
for Natural Gas units and H7001 for Propane Gas units . Replace the test
point screw ensuring no gas leaks .
Figure 7b - Check regulator pressure
14
WARNING
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

SPARK GAP

The gap between the spark electrode and the pilot should be 1/8" to
3/16" to produce a good spark . There should be no need to adjust this
(DO NOT ATTEMPT TO ADJUST THE GAP) . If under any circumstances
the piezo electric spark fails, the pilot cannot be lit manually .
Adjustment to the
1/8" to 3/16" Spark Gap
pilot is Not allowed
Figure 8 - Proper Spark Gap

BRIEFING THE CUSTOMER

WARNING
Do not add logs or ornaments such as pine cones,
vermiculite or rock wool. Using these added items
can cause sooting.
All instructions must be left in the possession of the user for safekeeping .
If at all possible, show the customer how to light and control the appli-
ance and show the customer how to remove and replace the surround
assembly and glass door assembly .
After commissioning the appliance, the customer should be instructed
on the safe use of the appliance and the need for regular servicing .
Frequency of service depends on usage, but MUST be carried out
at least once annually . Advise that cleaning of the appliance may be
achieved when the fire is cold using a damp cloth and mild detergent
on most surfaces .
Advise that the fireplace will emit a "newness" smell for a time after
initial commissioning and that extra ventilation may be needed during
this time . Recommend that a guard be used for the protection of the
young, pets, the elderly and the infirm .
Advise the user to never place any objects on top of the appliance or
obstruction this area in any way.
A periodic visual check of the pilot flame and the burner flame should
be carried out .