QuickSpecs

Technical Specifications

Operating Temperature
Shipping Temperature
Humidity
Shipping Humidity
Operating Vibration
Non-operating Vibration Sine 10-150 Hz 0.3g, Random 10-500 Hz at 0.5 Grms
Shipping Vibration
(packaged, on shock pallet)
Operating Shock
Non-operating Shock
Shipping Shock
(packaged, on shock pallet)
Altitude
Air Quality
Power Data (North America/Europe/Japan) maximum configuration
NOTE: This power information is for a maximum configuration using the default 208 - 240 Volt single-phase PDUs. Other PDUs may
use different plugs, voltages, etc. For more information on PDU support, please see the following URL:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/pdu.html
AC plug type
(quantity 2)
Number of phases
Rated current
Nominal Line Voltage
Range Line Voltage
Line Frequency
EVA P6000 Array Power, Heat and Current
50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft altitude (1.8° C/1,000 m)
-40° to 150° F (-40° to 66° C)
10% to 90% non-condensing
5% to 90% non-condensing
Sine 5-10 Hz 0.020" (0.5mm) double amplitude displacement, 10-500 Hz 0.1g, Random 10-500Hz at 0.15
Grms
Sine 5-150 Hz 0.5g, Random 0.86 Grms from 5-300 Hz, consisting of 5-100 Hz at 0.0059 g2/Hz and 100-
300 Hz at 0.000049 g2/Hz
5g half-sine 10mSec
8g half-sine 10mSec
Horizontal: 10-deg incline at 1m/Sec, Vertical rotational edge 0.15m
Up to 8,000 ft (2,400 m)
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or larger
North America - 3 wire NEMA No. L6-30P, 30 Amp (208 to 240V, 50-60Hz 30A)
Europe - 3 wire, 2 pole IEC 309, 30 amp, (220 to 240V 50Hz 32A)
NOTE: For other voltages, including 3-phase or 100-127V, see the PDU information for plug types at:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/pdu.html.
Single (3-phase PDUs are also available)
17A @ 200V-240V AC, 60Hz total, 4.25 A per power cord (2 PDUs)
34A @ 100-127V AC, 60/50Hz, 8.5A per power cord (2 PDUs)
NOTE: The current ratings are for a full 42U cabinet with default PDUs. Different PDUs have different
current/power ratings. The cabinet may be full of EVA and other equipment and actual current loads will
vary by configurations. For the individual EVA P6300/P6350 or EVA P6500/P6550 current loads, see the
table below.
North America - 208V or 230V or 120V
Europe - 230V
Japan - 206V or 108V
Latin America - 208V or 240V
187V to 256V or 90V to 127V
North America 60 Hz, Europe 50 Hz, Japan 50 or 60 Hz, Latin America 60K or 50Hz