HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
RESTORING DEFAULT VALUES
LOAD
FACTORY
DEFAULTS
2 SECS
IS THE PANEL LOCKED?
N
IS THE AUTO SET
LIGHT LIT?
N
66-2069—01
PRESS LOAD FACTORY DEFAULTS
FOR 2 SECONDS
Y
Y
RESET
rE
OR
LOAD
FACTORY
DEFAULTS
Fig. 17. Flow Chart 1 - Setting Factory Defaults.
DISPLAY SHOWS 'PL',
MEANING THE PANEL IS LOCKED
NORMAL OPERATION
DISPLAY SHOWS 'CF',
MEANING CONFIRM
PRESS RESET OR WAIT 4 SECONDS TO CANCEL
CHANGING THE AUTO SET VALUES
PRESS LOAD FACTORY DEFAULTS AGAIN TO CONFIRM
YOU WANT TO CHANGE THE AUTO SET VALUES
RELAY ON
16
RATIO
50%
0-20/4-20mA OPTION
4-20mA
FFRT
1 SEC
NORMAL OPERATION