Checking The Gas Supply; Factory Settings; Gas Inlet Working Pressure; Checking The Gas Rate - Vaillant ecoTEC plus 612 Instructions For Installation And Servicing

Wall hung room sealed fan assisted condensing boiler
Table of Contents

Advertisement

5.9

Checking the gas supply

5.9.1 Factory settings

Caution!
Before operating the boiler check the data
badge and ensure that the correct gas type
appliance has been installed.
The boiler is supplied ready adjusted and no further gas
adjustments are necessary, however both the gas inlet
working pressures and maximum gas rates should be
checked as detailed in 5.9.2 and 5.9.3.

5.9.2 Gas inlet working pressure

Check the inlet pressure as described below:
• Remove the front case from the boiler.
• Close the gas shutoff valve fitted to the boiler.
Fig. 5.13 Checking the gas supply pressure
• Loosen the sealing screw marked "in" (1) on the gas
valve assembly.
• Connect a digital or a U gauge (2).
• Open the gas shutoff valve fitted to the boiler.
• Put the boiler into operation (refer to the Instructions
for Use supplied with the boiler).
• Check the U gauge reading and ensure the inlet gas
pressure is between the pressures detailed below.
Instructions for installation and servicing ecoTEC
Natural gas:
DO NOT proceed with adjustment or attempt to
put the unit into service if the inlet working
pressure lies outside the 17–25 mbar range.
LPG:
DO NOT proceed with adjustment or attempt to
put the unit into service if the inlet working
pressure is lower than 37 mbar.
• Turn off the appliance, remove U gauge.
• Tighten the test point screw and check for leaks.
• Record appliance working gas inlet pressure (mbar) in
the Benchmark Installation, Commissioning and
Service Log Book.

5.9.3 Checking the gas rate

The boiler is fitted with a fully modulating automatic gas
valve which ensures that the precise air/gas ratio is pro-
vided under all operating conditions.
1
The gas rate has been set during production and does
not require adjustment.
The gas rate of the boiler should be checked with the
front case fitted as follows:
• Activate full gas rate mode by simultaneously pressing
the "+" and "–" buttons on the display system (for
ecoTEC plus 800 and pro boilers fully open the hot
water tap to maximum water flow rate).
• Wait at least 5 minutes, or until the boiler has reached
its operating temperature.
• With all other gas appliances turned off measure the
gas rate at the gas meter. Check that the gas rate is as
stated in Table 5.1.
Maximum
Appliance
input in kW
ecoTEC plus 612
ecoTEC plus 615
ecoTEC plus 618
ecoTEC plus 624
ecoTEC plus 630
ecoTEC plus 824
ecoTEC plus 831
ecoTEC pro 28
Table 5.1 Nominal gas rates
2
Caution!
If the measured gas flow volume lies outside
the tolerance limits specified in Table 5.1, do not
operate the appliance and inform the Vaillant
Customer Service.
Commissioning Part I 5
Nominal gas rate
(Tolerance 5 %)
net heat
Natural gas
3
in m
/h
12.2
1.3
15.3
1.6
18.4
1.9
24.5
2.6
30.6
3.2
23.5
2.5
31.6
3.3
28.6
3.0
Propane
in kg/h
0.95
1.19
1.43
1.90
2.38
1.82
2.46
2.22
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents