Flue Termination; Air Supply - Vaillant ecoTEC plus 612 Instructions For Installation And Servicing

Wall hung room sealed fan assisted condensing boiler
Table of Contents

Advertisement

3 General requirements
3.7

Flue termination

The following details refer to both flue systems.
a. The terminal must be located where the combustible
substances can escape freely at all times.
b. A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be
a nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a balcony,
above ground or above a flat roof to which people
have access then a suitable terminal guard must be
provided and fitted (made by Tower Flue
Components, Tonbridge, TN9 1TB, Model K3, plastic
coated).
A
G
F
J
E
Fig. 3.8 Flue termination
Note
Vertical flues must not terminate within
600 mm of an openable window, air vent or any
other ventilation opening.
The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any part of the building.
Terminal position
Directly below an opening, above an opening or hori-
A
zontal to an opening, air brick, opening window, etc.
B
Below gutters, soil pipes or drain pipes
C
Below eaves
D
Below balconies
E
From vertical drain pipes and soil pipes
F
From internal or external corners
G
Above ground, roof or balcony
H
From a surface facing a terminal
I
From a terminal facing a terminal
From an opening in the car port (e.g. door, window)
J
into the dwelling
K
Vertically from a terminal on the same wall
L
Horizontally from a terminal on the same wall
M
Distance from adjacent for vertical Flue
Table 3.4 Terminal position for a fan assisted concentric flue
14
B F
BCD
M
G
A
K
F F
A
L
A
G
Note
In addition, the terminal should not be nearer
than 150 mm to an opening in the building fab-
ric formed for the purpose of accommodating a
built-in element such as a window.
BS 5440–1: It is recommended that the fanned flue ter-
minal should be positioned as follows:
a) at least 2 m from an opening in the building directly
opposite, and
b) so that the products of combustion are not directed
to discharge across a boundary.
1) Dimensions B, C and D:
These clearances may be reduced to 25 mm without
affecting the performance of the boiler. In order to
ensure that the condensate plume does not affect
adjacent surfaces the terminal should be extended as
shown in Fig. 3.9.
2) Dimension F:
This clearance may be reduced to 25 mm without
L
affecting the performance of the boiler. However, in
K
order to ensure that the condensate plume does not
affect adjacent surfaces a clearance of 300 mm is
preferred. For IE, recommendations are given in the
current edition of IS 813.
mm
300
75
200
Fig. 3.9 Flue termination under balcony/eaves
200
25
300
3.8

Air supply

Detailed recommendations for air supply are given in
300
BS 5440: Part 2.
600
It is not necessary to have an air vent in the room or
1200
internal space in which the boiler is installed.
1200
1500
Cupboard or compartment ventilation
300
The boilers are very high efficiency appliances. As a con-
500
sequence the heat loss from the appliance casing during
operation is very low. For cupboard or compartment
installations it is therefore not necessary to provide any
high or low level permanent air vents for cooling purpos-
es.
Instructions for installation and servicing ecoTEC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents