Wiring Specification; Mechanics; Environmental Conditions; Trademarks - Bosch FMR-1000-RCMD Installation And Operation Manual

Remote command center
Table of Contents

Advertisement

Available languages

Available languages

16
en | Specifications
Current consumption at 24 V DC/FWR
11.1.1

Wiring Specification

Cable entries
Connections
Wire gauge
Wire type
Maximum number of annunciators per
system
Distance allowed between FACP and
annunciator
Maximum length of Option Bus wiring
11.2

Mechanics

Operating and display elements
Mounting holes back box
Housing material
Color
Dimensions (W x H x D)
Weight
11.3

Environmental Conditions

Environment
Operating temperature
Storage temperature
Relative humidity
Protection class per IEC 605029
11.4

Trademarks

Phillips is a registered trademark of the Phillips Screw Co.
F.01U.078.098 | 3.0 | 2011.11
Standby current
Alarm current
6 LEDs
LCD
Keys
Piezo
FMR-1000-RCMD
Back box
Installation and Operation Guide
30 mA maximum (only Power LED on)
120 mA maximum (with annunciator lit and piezo
on)
3 knockouts for 1/2 in. diameter conduit
connectors in the back, bottom and top side
2 connectors (4 terminals)
AWG 12 to 18 (diameter 3.25 mm
Non-shielded, four conductor wire
8 (FMR-1000-RA and/or FMR-1000-RCMD)
2000 ft (610 m)
4000 ft (1219 m), depending on cable gauge and
connected devices
Fire (red), Gas Alarm (blue), Power (green),
Supervisory, Silenced and Trouble (3 x yellow)
4 line x 20 character LCD display, backlit
Keys for Drill, Reset, Silenced, Acknowledge [ACK],
4 arrow keys
Built-in piezo sounder
2, spaced 5.5 in. (140 mm) apart
ABS-FR
Red
7.40 x 4.41 x 2.40 in. (188 x 112 x 61 mm)
7.40 x 4.41 x 1.89 in. (188 x 112 x 48 mm)
19.4 oz (550 g)
Indoor, dry
32 °F to 120 °F (0 °C to +49 °C)
-4 °F to 140 °F (-20 °C to +60 °C)
Up to 95%, non-condensing
IP 30
Remote Command Center
2
2
to 0.75 mm
)
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents