Remote Command Center
5

Wiring

DANGER!
Explosion and burn hazard. Do not short terminals.
Incorrect connections can result in damage to the unit and personal injury.
Before servicing this equipment, remove all power connections.
5.1

Option Bus Circuit Wiring Distance

Use four conductor, 18 AWG (0.8 mm
FACP. The total length of wire connected to the Option Bus terminals must not exceed 4000 ft
(1219 m), regardless of the wire gauge used.
The maximum length between any one device and the panel terminals depends on the current
drawn on the branch that the device is on. The current draw on a particular branch can be
found by adding together the individual current draws of each device connected to the
branch. Refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607) for detailed
wire length calculations.
5.2

Wiring Connections

The FMR-1000-RCMD is powered by either of the following power outputs from the FPA-1000:
or UL listed external power supply with common reference ground with the FPA-1000:
To wire the FMR-1000-RCMD:
1.
2.
3.
Legend
GND
V+/PWR
Y
G
P3
P7
4.
5.
6.
7.
Bosch Security Systems, Inc.
12 V DC power (Option bus)
24 V FWR unfiltered Aux power output
12 V DC power
24 V DC power.
Power down the control panel.
Route the wiring from the FACP to the annunciators.
Bring the wiring through one of the knockouts in the annunciator's base (surface
mounting) or the 3 gang electrical box (flush mounting). Refer to Figure 4.2 on Page 8 for
wire entrance location in the back box.
Ground
Power supply
Yellow, Data OUT
Green, Data IN
Power supply
connection
Data connection
Connect the wiring to the FMR-1000-RCMD terminals. Refer to Figure 5.1.
For surface mounting with back box: Secure the base. Use the bubble level to make sure
that the back box is perfectly horizontal. Refer to Figure 4.2 on Page 8.
Fasten the annunciator unit with the four mounting screws using a Phillips (cross-
headed) screwdriver. Secure the screw for the earth ground connection. Refer to
Place the cover frame onto the base along the top side. Press the bottom part until it
snaps into place.
Installation and Operation Guide
2
) or larger wire to connect Option Bus devices to the
P3
GND PWR+
Y
G
B
R
Figure 5.1 Wiring Connections
Wiring | en
9
P7
Y
G
F.01U.078.098 | 3.0 | 2011.11