Control Board Check - Hoshizaki KMS-1122MLH Service Manual

Modular crescent cuber serenity series
Hide thumbs Also See for KMS-1122MLH:
Table of Contents

Advertisement

C. Control Board Check
Before replacing a CB that does not show a visible defect and that you suspect is bad,
always conduct the following check procedure. This procedure will help you verify your
diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB while
CB is beeping. WARNING! Risk of electric shock. Care should be taken
not to touch live terminals. Once reset, the appliance starts at the 1-min.
fill cycle. For audible alarm information, see "III.B. LED Lights and Audible
Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10, and S5 dip
switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are
cleaning adjustments and the settings are flexible. For factory default settings,
see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, CB
control voltage is good, continue to step 3. If the red "POWER OK" LED is off, check
CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary
circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K1 connector pin #10 (BR) to a neutral (W) for 115VAC. Always
choose a neutral (W) to establish a good neutral connection when checking voltages.
For additional checks, see "II.G.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control
switch is in the "ICE" position, then press the "OUTPUT TEST" button. The correct
lighting sequence is 1, 4, 3, 2. Note that the order of the LEDs from the outer edge of
CB is 1, 4, 3, 2. Components (e.g., compressor) will cycle during the test. Following
the test, the appliance resumes operation. If the LEDs do not light as described above,
replace CB.
4) To verify voltage output from CB to the components, slide CB K1 connector out far
enough to allow multimeter lead contact. With the appliance in the cycle to be tested,
check output voltage from the corresponding pin on CB K1 connector to a neutral (W).
If output voltage is not found and the appropriate LED is on, replace CB.
5) Check CB control connectors K3, K4, and K5 for correct VDC per table below.
Note: Pin #1 is DC ground (GND) on each connector.
K3 Thermistor
Pin #
VDC
#1 to #2
5VDC
#1 to #3
5VDC
#2 to #3
0VDC
Legend: CB–control board; CT–control transformer
ALARM RESET
K4 Jumper
Pin #
VDC
#1 to #2
5VDC
#1 to #3
5VDC
#2 to #3
0VDC
16
OUTPUT TEST
10
K5 Float Switch
9
8
7
6
5
4
3
2
1
ON
Pin #
VDC
#1 to #2
1.2VDC
#1 to #3
2VDC
#2 to #3
1.2VDC
Thermistor
Jumper
ON
Float Switch
1 2 3 4 5
CB