INSTALLATION
INSTALL THE MOUNTING PLATE
1
• Always mount the mounting plate horizontally.
• Attach the mounting plate at the selected location
with screws supplied with the unit.
• Be sure that the mounting plate has been
attached firmly enough to withstand the weight
of an adult of 130 lbs. Also, the weight should be
evenly shared by each screw.
INSTALL THE TUBING HOLE
2
• Make the tubing hole in the wall at a slight
downward slant to the outdoor side.
Hole is 2" diameter for 10K and 14K BTU
models and 2
1
" diameter for
2
20K BTU models.
• To let water drain and prevent damage to wiring
and tubing, insert a 2
1
length equal to the wall depth. Insert the tubing
and wiring through the pipe.
• Copper tubing should be capped until ready to
install flare fitting, to prevent contamination.
INSTALL THE DRAINAGE HOSE
3
• For good drainage, the drain hose should be
placed at a downward slant.
• Do not wrench or bend the drain hose or allow
it to contact standing water.
• The extended drainage tube in the room should
be wrapped with the insulating materials.
Wrenched
Installation Instructions
3" from right
edge to center of
right tubing hole
1
" from bottom
1
2
edge to center of
right tubing hole
plastic pipe, cut to a
2
Bend
Flooded
INSTALL THE CONNECTION TUBING
4
• Connect the copper tubing with the relevant union
tubes of the indoor unit and tighten the flare nut
of the connection tubes.
NOTE: Be careful when bending the connection
tubes to avoid damaging them.
1. Align the center of the tube flare with the relevant
valve.
2. Screw in the flare nut by hand and then tighten
the nut with spanner and torque wrench. See the
table below for the correct torque.
3. Connecting tube specifications are shown below:
Specifications
Design Length
Extra Refrigerant Charge
Per Ft. Above Design Length
Outer Diameter Liquid Pipe
Outer Diameter Gas Pipe
Max. Distance Height
Max. Distance Length
NOTE: Exceeding tightening torque will damage
the copper tubing.
Tightening torque table
Tubing OD
1/4
3/8
1/2
5/8
Flare nut
11
10,000/14,000
20,000
BTU Units
BTU Units
20 ft.
26.2 ft.
0.16 oz./ft.
0.54 oz./ft.
1/4
3/8
1/2
5/8
33 ft.
33 ft.
68 ft.
98 ft.
Tightening torque (in./lb.)
140–170
270–310
440–480
530–570
Spanner
Joint
Torque wrench