3-3. Remove the Brackets Used for Transport

After installing the unit, remove the
2 transport brackets from the front
and rear (4 brackets total).

3-4. Routing the Tubing

The tubing can be routed out either from the front or from the bottom. (Fig. 3-6)
The connecting valve is contained inside the unit. Therefore, remove the front panel. (Fig. 3-6)
(1) If the tubing is routed out from the front, use cutting pliers or a similar tool to cut out the tubing outlet slit (part
indicated by
) from the tubing cover. (Figs. 3-6 and 3-7)
Remove 2 screws
(2) If the tubing is routed out from the bottom, remove
the slit part (
).
Use a drill bit approximately 13/64" dia. to create
holes at the 4 slit hole indentations (openings).
Punch out the slit part (
Be careful not to damage the base plate.
(Fig. 3-5)
Remove the 2 screws
(8 screws total)
Front
Bottom
Remove 11 panel
screws from front
panel
Tubing cover
Use cutting pliers or similar
tool to cut cover out
Fig. 3-6
).
25
Remove the 2 transport brackets from
the front and rear (4 brackets total)
Fig. 3-5
Indentation
(4 locations)
Fig. 3-7