Appendix D-Quick Motor Test Procedure - Carrier 58MVP Troubleshooting Manual

Variable-speed 2-stage electronic condensing furnace
Table of Contents

Advertisement

In an effort to provide a method of troubleshooting inducer and blower motor by themselves, the following procedure may save you some time
in the event any of the following fault codes are the reason for service call (12, 32, 41, 42, or 44). If you get any other fault code, you should
use main troubleshooting guide to isolate problem.
STEP
1.
Turn power off, remove blower access panel, and disconnect R thermostat lead.
2.
Turn power on and depress door switch. Use a piece of tape to hold switch closed.
3.
Put setup switch SW-6 for COMPONENT TEST in ON position.
4.
After COMPONENT TEST is completed, does Fault Code 11 flash?
Turn power off, put setup switch SW-6 for COMPONENT TEST in OFF position, and reconnect R
5.
thermostat lead to furnace control board.
Replace blower access panel and turn power on. Wait a few sec, then reset thermostat. Observe
6.
operation of furnace through 1 heating cycle.
7.
Go to page number indicated in Index for START HERE section.
8.
Does Fault Code 42 flash?
9.
Does inducer motor MTR1 turn on and come up to speed?
10.
Does inducer wheel rub against inducer housing?
11.
Does inducer wheel turn freely?
12.
Do you have 120v between I1 and I2 on furnace control board?
13.
Do you have 120v between terminals PL7-6 and PL7-12?
You have an open wire or bad terminal on either the BLACK or WHITE wire between furnace con-
14.
trol board and inducer motor MTR1.
15.
Are all pins and wire leads intact on connectors between furnace control board and inducer motor?
16.
Fix problem.
17.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
Check Inducer PW line. To do this, connect a DC voltmeter across terminals PL7-2 BROWN (+)
and PL7-10 YELLOW (-) on inducer motor. Repeat COMPONENT TEST by turning setup switch
SW-6 OFF and then back ON. Does voltage across PL7-2 and PL7-10 change between states as
18.
shown below?
• State 1—OFF (-0.1 — 0.1 vdc)
• State 2—LOW (2.0 — 3.0 vdc)
• State 3—HIGH (7.0 — 8.0 vdc)
Replace inducer motor or inducer motor assembly. Inspect electronics portion of failed motor for
19.
water damage. If present, find source of water and fix. Check A-coil and/or humidifier.
Disconnect PL7 from inducer motor and connect a DC voltmeter across terminals PL7-2 BROWN
(+) and PL7-10 YELLOW (-). Repeat COMPONENT TEST by turning setup switch SW-6 OFF and
then back ON. Does voltage across PL7-2 and PL7-10 change between states as shown below?
20.
• State 1—OFF (-0.1 — 0.1 vdc)
• State 2—LOW (6.0 — 7.0 vdc)
• State 3—HIGH (10.5 — 11.5 vdc)
Connect a DC voltmeter across terminals PL1-6 BROWN (+) and PL1-4 YELLOW (-) on furnace
control board. Repeat COMPONENT TEST by turning setup switch SW-6 OFF and then back ON.
Does voltage across PL1-6 and PL1-4 change between states as shown below?
21.
• State 1—OFF (-0.1 — 0.1 vdc)
• State 2—LOW (6.0 — 7.0 vdc)
• State 3—HIGH (10.5 — 11.5 vdc)
22.
Replace furnace control board.
You have an open wire or bad terminal on either the BROWN or YELLOW wire between connectors
23.
PL1 and PL7. Repair it or replace main harness.
Check RPM feedback line. To do this, connect a DC voltmeter across terminals PL7-2 BROWN (+)
and PL7-1 ORANGE (-) on inducer motor. Repeat COMPONENT TEST by turning setup switch
SW-6 OFF and then back ON. Does voltage across BROWN and ORANGE wires change between
24.
states as shown below?
• State 1—OFF (11.5 — 12.5 vdc)
• State 2—LOW (10.2 — 11.2 vdc)
• State 3—HIGH (8.4 — 9.4 vdc)
Connect a DC voltmeter across terminals PL1-6 BROWN (+) and PL1-5 ORANGE (-) on furnace
control board. Repeat COMPONENT TEST by turning setup switch SW-6 OFF and then back ON.
Does voltage across BROWN and ORANGE wires change between states as shown below?
25.
• State 1—OFF (11.5 — 12.5 vdc)
• State 2—LOW (10.2 — 11.2 vdc)
• State 3—HIGH (8.4 — 9.4 vdc)
You have an open wire or bad terminal on ORANGE wire between connectors PL1 and PL7. Repair
26.
it or replace main harness.
27.
Does Fault Code 41 flash?
28.
Does blower motor MTR2 turn on and come up to speed?
29.
Remove tape from door switch and turn power off at main disconnect.
Appendix D
Quick Motor Test Procedure
ACTION
37
YES
NO
GO TO
2
3
4
5
8
6
7
INDEX
9
27
24
10
16
11
12
19
13
16
15
14
16
18
16
17
INDEX
19
20
17
19
21
23
22
17
17
25
19
22
26
17
28
7
48
29
30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents