Engine Temperature & Oil Pressure Calibration
To accurately calibrate the controller's temperature sensor, an external temporary engine mounted
temperature gauge is required. The external temperature gauge should be connected as close as possible
to the temperature sender.
To accurately calibrate the controller's pressure sensor, an external temporary engine mounted pressure
gauge is required. The external pressure gauge should be connected as close as possible to the pressure
sender.
Engine Temperature
Oil Pressure
Note:
MN2408
ENGINE TEMP
127
Displays the type of calibration function.
Displays the calibration correction factor number (0-255) used to obtain the correct Temperature or Pressure reading.
Displays the actual temperature or pressure measurement shown on the display menus.
This reading may be calibrated higher or lower by changing the correction factor number.
The engine temperature analog circuit must be calibrated with the engine temperature sender mounted on the engine.
Connect a temporary engine mounted temperature gauge of suitable accuracy and start the engine. After the engine
reaches normal operating temperature, enter the programming mode and scroll to the "Engine Temperature Offset"
calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while
observing the displayed temperature. Adjust the correction factor number to obtain the identical temperature reading as
measured with the external temperature gauge. With the correct temperature displayed, press the "Enter" push-button to
accept the correction factor number. Record the correction factor on the programming sheet for future reference.
Connect a temporary engine mounted pressure gauge of suitable accuracy and start the engine. After the engine
reaches normal operating pressure and temperature, enter the programming mode and scroll to the "Engine Pressure
Offset" calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number
while observing the displayed pressure. Adjust the correction factor number to obtain the identical pressure reading as
measured with the external pressure gauge. With the correct pressure displayed, press the "Enter" push-button to
accept the correction factor. Record the correction factor on the programming sheet for future reference.
Engine
Sender
Temperature
Resistance
5F
5C
Ohms
392
200
374
190
356
180
338
170
320
160
302
150
284
140
266
130
248
120
230
110
212
100
194
90
176
80
150
70
140
60
122
50
104
40
86
30
1486
68
20
2322
50
10
3644
32
0
6284
Sender resistance data shown are for Oil Pressure Sender p/n-003654 (Thompson p/n), Manufacturer- Datcon, p/n
102227. Datcon Sender must be used with MEC software version 1.81 or greater (previous software versions cannot be
used).
955C
Oil
Pressure
KPA
PSI
20
1034
150
24
965
140
28
896
130
33
827
120
39
758
110
46
689
100
55
621
90
65
552
80
76
483
70
90
414
60
106
345
50
147
276
40
197
207
30
290
138
20
426
69
10
622
952
Sender
Resistance
Ohms
38
42
48
54
62
70
79
89
101
114
127
142
160
183
206
Operation 4‐29