Honeywell TB7100A1000 MultiPRO Product Data page 14

Multispeed and multipurpose thermostat for conventional, heat pump, fan coil and ptac systems
Hide thumbs Also See for TB7100A1000 MultiPRO:
Table of Contents

Advertisement

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Installer
Setup
Installer Setup
Number
Name
0349
Auto Fan Reset
0535
Temporary
Occupied Duration
Limit
0540
Number of Periods 4
0580
Minimum
Compressor Off
Time
0600
Heat Temperature
Range Stops
0610
Cool Temperature
Range Stops
0640
Clock Format
0650
Extended Fan-on
time Heat
0660
Extended Fan-on
time Cool
0670
Keypad Lockout
0680
Temperature
Control Heat
0685
Recovery Heat
Ramp Rate
0690
Temperature
Control Cool
0695
Recovery Cool
Ramp Rate
63-2675—03
Table 6. Installer Setup Menu. (Continued)
Default
Setting
All Settings
0
0—Inactive
1—Reset back to Auto after 2
hours
2—Reset back to Auto after 4
hours
3
0–12 hours
2—2 Periods
4—4 Periods
5
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
90
40 to 90°F (4 to 32°C)
50
50 to 99°F (10 to 37°C)
12
12—12 Hour
24—24 Hour
0
0—Off
90—90 seconds
0
0—Off
40—40 seconds
0
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Partial Lockout 3
4—Fully Locked
2
1—Less Aggressive
2—Standard
3—More Aggressive
5
0-20°F/hour
2
1—Less Aggressive
2—Standard
3—More Aggressive
3
0-20°F/hour
The timer will be set after the user selects the
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 2 hour timing begins.
The timer will be set after the user selects the
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 4 hour timing begins. Only available for fan coil
or PTAC applications (ISU 0170)
0 means no limit.
Does not appear if Non-programmable is chosen (ISU
0160).
Applies to all days of the week. If 2 is selected the
Cancel Period option will not appear on the display.
Only shown if system has cool stages in CNV, Heat
Pump, PTAC (ISU 0170).
Only shown if system has heat stages (ISU 0170).
Only shown if system has cool stages (ISU 0170).
Not displayed if fan set to fossil or cool only systems
(ISU 0170)
Only shown if system has cool stages. (ISU 0170)
Unlocked: All functions accessible.
Partial 1: Locks out schedule and system changes.
Partial 2: Locks out schedule, system, and fan
changes.
Partial 3: Locks out schedule, system, fan, and up/
down arrow changes.
Full: Entire interface locked/non-functional.
Only shown if system has heat stages (ISU 0170).
Only integral gains are affected by this setting. The
setting affects control operation in all control regimes
(not just recovery or setpoint change).
Only shown if system has heat stages (ISU 0170).
0 disables the ramped recovery (step setpoint change
at period start time).
Only shown if system has cool stages (ISU 0170).
Only integral gains are affected by this setting. The
setting affects control operation in all control regimes
(not just recovery or setpoint change).
Only shown if system has cool stages (ISU 0170).
0 disables the ramped recovery (step setpoint change
at the period start time).
14