TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND TESTS (TABLE 6)
Use the Installer System Test to test the heating, cooling and
fan. Refer to the latter portion of Table 6.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
Installer
Setup
Installer Setup
Number
Name
0120
Date (Year Upper)
0130
Date (Year Lower)
0140
Date (Month)
0150
Date (Day)
0160
Schedule Options
0170
System Selection
0180
Heat Fan Operation 0
0185
Pre-occupancy
Purge Duration
0190
Reversing Valve
O/B
0220
Cycles Per Hour
(CPH) for first stage
cooling/compressor
0240
CPH for first stage
heat
0270
CPH for Em Heat
0280
Continuous
Backlight
0300
Changeover
63-2675—03
Table 6. Installer Setup Menu.
Default
Setting
All Settings
20
20—21
08
00-99
6
1-12
15
1-31 (Month Dependent)
4
0—Non-Programmable
4—Programmable
1
1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux Heat
10—PTAC 1H/1C (Hi speed, Lo
speed Fan)
11—PTAC 2H/1C (Hi speed, Lo
speed Fan)
0—Fossil
1—Electric
0
0—no duration
1—one hour
2—two hours
3—three hours
0
0—O (O/B On Cool)
1—B (O/B On Heat)
3
1-6
5
1-12
9
1-12
0
0—No
1—Yes
1
0—Manual
1—Auto
IMPORTANT
Use Installer System Test to test heating, cooling and
fan. The setting chosen for System Type (ISU 0170)
can prevent some System Test Numbers from
appearing.
NOTE: Unless otherwise noted, setup items are accessible
through only the Installer setup and not the User
setup.
Available year range: 2001 - 2178
Available year range: 2001 - 2178
Relay Y is used for 2 pipe fan coil output relay.
Only shows up if conventional system with heat
stages and fan capability is selected (ISU 0170). If
heat pump is selected, fan defaults to electric. If fan
coil or PTAC modes are selected, fan defaults to
electric (does not show up).
Shown only if system has fan and schedule is
programmable (ISU 0160).
Pre-occupancy purge is enabled by a nonzero
duration.
Only shown if heat pump or PTAC system is selected.
Only shown if system has cool stages (ISU 0170).
Shown for heat pump, fan coil, PTAC, and
conventional cooling stages.
Only shown if system is conventional with heat
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
Only shown if HP with reheat, 2 pipe fan coil with
reheat, and PTAC with reheat (ISU 0170).
Always shown; however, if AC power is not present,
the option is overridden and normal backlight
operation occurs.
Only shown if system has both heat and cool stages
(ISU 0170). Shown for CNV, HP, PTAC and 4 pipe fan
coil (ISU 0170). Not shown for 2 pipe fan coil modes.