Chimney Connection; Vertical Exhaust Gas Vent - Kenmore 153.337021 Use & Care Manual

40 & 50 gallon tall
Hide thumbs Also See for 153.337021:
Table of Contents

Advertisement

The ventconnector mustbe accessible for cleaning,
inspection, and replacement.
Ventconnectors cannot p assthrough a nyceiling, floor,
firewall, orfirepartition.
It isrecommended
(but n otmandatory)
thata minimum 1 2
inches o fvertical ventpipe beinstalled onthedrafthood
prior t oanyelbow inthevent s ystem.
IMPORTANT:
Existing ventsystems m ustbe inspected for
obstructions,
corrosion, andproper installation.
Chimney
Connection
IMPORTANT: Before connecting a vent to a chimney, make sure
the chimney passageway
is clear and free of obstructions. The
chimney must be cleaned if previously
used for venting solid
fuel appliances or fireplaces. Also consult local and state codes
for proper chimney sizing and application
or, in the absence
of local and state codes, the "National Fuel Gas Code", ANSI
Z223.1 (NFPA 54)-current edition.
The connector must be installed above the extreme bottom
of the chimney
to prevent potentially
blocking
the flue
gases.
The connector
must be firmly
attached
and sealed
to
prevent it from falling out.
To aid in removing the connector, a thimble or slip joint may
be used.
The connector must not extend beyond the inner edge of
the chimney as it may restrict the space between it and the
opposite wall of the chimney (Figure 20).
3 FT. MINIMUM
SUPPORT
MAINTAIN
CLEARANCE*
f
LISTED
LINED
CHIMNEY
2 FT. MINtMUM
ABOVE
ANY
OBJECT
WITHIN
10FT.
HORIZONTALLY
DO NOT
EXTEND
BEYOND
EDGE
OF CHIMNEY
CONNECTOR
CHIMNEY
TERMINATION
VENT
SYSTEM
FIGURE 20.
Do not terminate the vent connector in a chimney that has not
been certified for this purpose. Some local codes may prohibit
the termination of vent connectors in a masonry chimney.
Vertical
Exhaust
Gas Vent
Vertical exhaust gas vents must be installed with U.L. listed type B
vent pipe according to the vent manufacturer's instructions and the
terms of its listing.
It must be connected
to the water heater's
draft hood by a
listed vent connector or by directly originating at the draft hood
opening.
Vertical gas vents must terminate with a listed cap or other roof
assembly
and be installed according
to their manufacturer's
instructions.
Gas vents
must
be supported
to prevent
damage,
joint
separation,
and maintain clearances to combustible
materials
(Figures 21 and 22).
IMPORTANT: This gas vent must be terminated
in a vertical
position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used as a
passageway for the installation of a gas vent (Figure 22).
Common (combined) venting is allowable with vertical type B
vent systems and lined masonry chimneys as tong as proper
draft for the water heater is established
under all conditions of
operation. CAUTION: DO NOT common vent this water heater
with any power vented appliance.
Figures 20-22 are examples
of vent pipe system installations
and may or may not be typical for your specific application.
Consult the "National Fuel Gas Code", NFPA 54, ANSI Z223.1-
current edition and the guidelines
set forth by prevailing
local
codes.
SUPPORT
STRAP
*MAINTAIN
CLEARANCE
±
t
--
LISTED
VENT
CAP
L!__
_'
FT. MINIMUM
ABOVE
ANY
OBJECT
3 FT. MINIMUM
WITHIN
10 FT. HORIZONTALLY
TYPE B DOUBLE
WALL VENT PIPE
_1.
**MAINTAIN
VENT
1
VERTICAL
GAS
VENT
SYSTEM
WITH
TYPE
B DOUBLE
WALL
VENT
PIPE.
FIGURE 21.
MAINTAIN
MANUFACTURER'S
SPECIFIED
MINIMUM
CLEARANCE
SUPPORT
*MAINTAIN
CLEARANCE
J_
-_'_LISTED
VENT CAP
"MAINTAIN
SPECIFIED
CLEARANCE
VENT
CONNECTOR
1/4 IN. PER FT.
MINIMUM
CONNECTOR
UNUSED
CHIMNEY
--L'-_FLUE
OR MASONRY
ENCLOSURE
21
VENTING THROUGH A CHIMNEY WITH
TYPE B DOUBLE WALL VENT PIPE.
FIGURE 22.
, Maintain vent pipe clearance requirements to local, state and/or the
"National Fuel Gas Code", ANSI Z223.1(NFPA 54)-current edition.
** NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel-Buming Appliances states that these chimneys are intended to
be installed in accordance with the installation instructions provided
with each chimney support assembly. Minimum air space clearance to
combustible materials should be maintained as marked on the chimney
sections.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

153.337041

Table of Contents