Allowable refrigerant piping length and height difference
7.
a. Allowable pipe length and height difference
Single way total pipe length
Single way max. pipe length
Main pipe between outdoor to 1
Pipe length between outdoors
Height difference between indoor and
outdoor
Height difference between outdoors(in the same system)
st
Max. pipe length from 1
branch pipe to indoor
Height difference between indoors
b. Pipe length between outdoors
outdoor1
Gas/liquid pipe:
Oil equalization pipe:
height difference between outdoors: h < 5m
Note: a. HZG-30/A includes HZG-20/A;
b. The connection pipe among outdoors can not be higher than the stop valve position;
c. The connection pipe among outdoors should be horizontal or be in a certain angle as
the below figure (less than 15degree).
st
branch
Outdoor is upper
Outdoor is lower
outdoor2
L2+L3 < 10m
L1 < 10m,
L5+L6 < 10m
94
300m
Max. 150m
Max. 90m
st
Less than 10m to 1
branch pipe
Max. 50m
Max. 40m
Within 5m (better be horizontal)
Max. 40m
Max. 15m
outdoor 3
3
2st gather pipe
1st gather pipe