Trouble-Shooting - RBI DOMINATOR Series Installation And Operation Manual

Dominator series finned copper gas boilers (model db) & water heaters (model dw)
Table of Contents

Advertisement

PROBLEM
No Power To Unit
No Action On Call For Heat
No Power To Pump
No Power to Power Venter
Power Venter On,
No Action From Unit
No Power To Blower(s)
Unit Does Not Spark
DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS

Trouble-Shooting

POSSIBLE CAUSES
Power not connected
External circuit breaker open
Relay board fuse (24V) blown
Transformer circuit breaker open
(4 stage)
Primary limit or other
control/interlock open
Low water cutoff open
Stage control sensor(s) not wired
or are malfunctioning
Stage control malfunction
Pump contact not wired
Stage control malfunctioning
Pump malfunctioning
Power venter contact not wired
Power venter not wired to
external power
Relay fault
Power venter fault
Power venter interlock open
Power venter interlock not wired
Blower(s) not plugged in
Relay fault
Blower(s) malfunctioning
Fault in prepurge circuit
Incorrect spark gap or shorted
ignitor lead
Bad ground on fl ame sense
module
Low air (blocked fl ue/inlet)
condition
CORRECTIVE ACTION
Wire unit to line voltage
Reset breaker
Replace fuse
Reset breaker
• Check indicator board, reset limit
or control or resolve problem as
applicable
• If not resolved, check wiring and
condition of limit.
• Check circulating pump
• Check pump contact in J-box
• Check LWCO wiring and condition
• Wire sensor(s) to J-box or replace
as necessary
• Check error message on control,
refer to control documentation
Replace stage control
Wire pump contact to J-box
Replace stage control
Replace pump
Wire power venter contact to J-box
Wire power venter as shown in
connection diagram
Replace relay
Replace power venter
• Check indicator board for power
vent indication
• If indication exists, check fl ue or
chimney for blockage
Wire power venter interlock as
shown in connection diagram
Plug in blower(s)
Replace blower relay
Replace blower(s)
Replace timer board
Adjust ignitor rod or correct short
Check ground connections,
adjust as necessary
• Check indicator board for low air
indication
• If condition exists, check inlet, fl ue,
chimney for blockage
• Check combustion air/ventilation
openings in space
• Check inlet air fi lter, clean/replace
as necessary
Page 37