Electrical Wiring; General Operation - RBI DOMINATOR Series Installation And Operation Manual

Dominator series finned copper gas boilers (model db) & water heaters (model dw)
Table of Contents

Advertisement

WARNING: Never use an open fl ame to test for
gas leaks. Always use an approved leak
detection method. Failure to comply with this
warning can cause extensive property damage,
severe personal injury or death!
Whenever the gas supply piping is pressure tested the
boiler/water heater gas controls must be protected. If the
test pressure is equal to, or less than 1/2 psig, 3.5 kPa
isolate the boiler/water heater by closing it's manual shut
off valve, see Figure 16. If the test pressure is greater
than, or equal to 1/2 psig, 3.5 kPa, disconnect the
boiler/water heater and its individual shut-off valve.

ELECTRICAL WIRING

Electrical Power Connections
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation! Verify proper
operation after servicing.
ATTENTION. Au moment de l'entretien des
commandes, étiquetez tous les fi ls avant de les
débrancher. Des erreurs de câblage peuvent
entraîner un fonctionnement inadéquat et
dangereux. S'assurer que l'appareil fonctionne
adéquatement une fois l'entretirn terminé.
The electrical connections to this boiler/water heater
must be made in accordance with all applicable local
codes and the latest revision of the National Electrical
Code, ANSI /NFPA-70. Installation should also conform
with CSA C22.1 Canadian Electrical Code Part I if
installed in Canada.
Install a separate 120 volt 15 amp or 20 amp circuit
breaker for the boiler/water heater and pump, see Table
11. A properly rated shut-off switch should be located
at the boiler/water heater. The boiler/water heater must
be grounded in accordance with the authority having
jurisdiction, or if none, the latest revision of the National
Electrical Code, ANSI/NFPA-70.
Table 11 - Dominator Electrical Requirements
Dominator
Model
DB/DW 300-600
DB/DW 750-900
DB/DW 1050-2100
*Use separate circuit breaker that is properly sized for
pump and pump contactor.
DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS
Recommended
Circuit Breaker
*Running
(Amps)
Amps
15
3.9
15
6.0
20
11.4
Line voltage fi eld wiring of any controls or other devices
must conform to the temperature limitation of type T wire
at 95°F, 35°C above room temperature. Use copper
conductors with a minimum size of #14 awg. Use
appropriate wiring materials for units installed outdoors.
The wire size must be compatible with the total amp
draw of the circuit.
Refer to the wiring diagram supplied with the boiler/
water heater for proper wiring connections.

GENERAL OPERATION

WARNING: Before proceeding read and fully
understand the instructions contained in this
manual. Do not attempt to operate this boiler/
water heater if it has not been installed in
accordance with the guidelines set forth in this
manual. Failure to comply with this warning can
result in extensive property damage, severe
personal injury or death!
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas control valve to the
appliance. Do not interrupt water fl ow through the boiler/
water heater.
En cas de surchauffe ou si l'alimentation en gaz ne
s'arrête pas, fermez manuellement le robinet d'arrêt de
l'admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly fi ll the boiler
and all of the radiation with water. Ensure that all bleed
and drain valves are closed.
Adjust the make-up water pressure regulator so a
minimum 12 psig, 82.7 kPa system pressure is
maintained at the highest point in the system piping. If
a make-up water pump is used adjust it to maintain a
minimum 12 psig, 82.7 kPa system pressure.
Open the system bleed and drain valves, one at a time,
to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30
minutes and bleed the system piping using the bleed
valves. If strainers are used in the system piping, the
make-up water valve should be closed and the strainers
checked and cleaned.
The system expansion tank should be checked to
ensure that the correct water level in the tank is
maintained. The tank should be less than half full of
water with the system full and adjusted to the correct
operating pressure.