Startup And Checkout; Operation; Identifying Dip Switches - Honeywell MiniZone EMM-3U Product Data

Universal electronic minizone panel
Table of Contents

Advertisement

24 Volt Equipment
R on Fan Center for AC
Compressor Relay
Fan Relay
This diagram shows the typical
air conditioning system and
hydronic zone valve hookup
using common dampers and
single stage thermostats.
For specific instructions, refer
to Installation Instructions.
V8043E
Fig. 19. EMM-3U with Air Conditioning Zoned with Dampers and Hydronic Heat Using V8043 Zone Valves.

STARTUP AND CHECKOUT

After the installation is complete, verify correct operation:
1. Place the Em Ht switch in the Off (down) position.
2. Verify that DIP switches are set correctly.
3. Turn on power to the EMM-3U Panel and set the ther-
mostats so no zones are calling.
a. EMM-3U enters the Purge Mode, opening all damp-
ers and operating the fan for two or three and one-
half minutes (configurable). In Purge, damper LEDs
are green to indicate the dampers are open.
NOTE: If a Discharge Air Temperature Sensor is not con-
nected to the panel, the purge LED flashes in all
modes other than Purge.
b. Press the Purge Override button on the panel to exit
the Purge mode early.
4. Set the zone one thermostat to heat and raise the set-
point to call for heat.
HEAT
COOL
PURGE
R
/R
C
H
JUMPER
EQUIPMENT
R
C
R
H
W
1
MOMENTARY PUSHBUTTON SWITCHES:
W
2
BOOT
USED TO CLEAR THE SYSTEM AND MICROPROCESSOR.
E
PURGE OVERRIDE USED TO BYPASS THE PURGE CYCLE WHILE TROUBLESHOOTING.
B
DIP Switches (see Installation Instructions for details):
O
1, 2, 3: Set to off for 1 stage heat and cool
Y
1
4: Set to on for conventional equipment
Y
5: Set to on for 160 F high limit
2
6: Set to on for 40 F or off for 48 F
G
7: Set to on
8: Set to on for no purge fan after call for heat or cool
9: Set to on
10: Set to on
11: Set to on
12: Set to on
ZONE 1
1
R
C
W1/E
Y1
G W2Y2
O/B
L
M6M4M1
Rc
Rh
W
Y
G
Zone 1 Thermostat
4 5 6 Z
1 2 3 X
Power-open
Power-closed
(Opposed Blade
Damper Motors)
EMM-3U UNIVERSAL ELECTRONIC MINIZONE™ PANEL
FAN
EM. HEAT ZONE 1
ZONE 2
O
N
1
2 3 4 5 6 7 8 9 101112
ZONE 2
1
R
C
W1/E
Y1
G W2Y2
O/B
L
M6M4M1
Rc Rh
W
Y
G
Zone 2 Thermostat
Th/Tr
Th
Th
V8043F
Power-closed
Spring-open
(Model ZD)
5. Verify that the heat LED is red and the zone one damper
remains green while the other damper LEDs turn off.
6. Raise zone two setpoint to call for heat. Lower zone one
setpoint to stop the call for heat to that zone.
7. Verify that zone one LED turns off and zone two LED
turns green.
8. Repeat for zones two and three.
9. Alternately, set the System switch to Cool, and lower the
setpoint to call for cooling.
10. Verify that the green cool LED illuminates.

OPERATION

Identifying DIP Switches

This panel has one bank of 12 DIP switches numbered
starting with 1 on the left. The switches are shipped in the On
(Up) position. See Fig. 13 and Tables 4 and 5.
11
ZONE 3
ON
BOOT
PURGE
OVERRIDE
EM
HEAT
OFF
DATS
DATS
ZONE PANEL
TRANSFORMER
R
C
24 VAC
40VA
ZONE 3
1
R
C
W1/E
Y1
G W2Y2
O/B
L
M6M4M1
Rc Rh
W
Y
G
Zone 3 Thermostat
Th/Tr
V8043F
Power-closed
Spring-open
(Model ARD)
Discharge Air
Temperature
Sensor
(See C7735
Installation
Instructions
for further
information.)
C R
24 Volt 40 VAC
Transformer
1 Leave this jumper
disconnected.
ZONE DAMPER MOTORS
M1 - common
M4 - power open
M6 - power closed
M20888
68-0237-2