Controller Pcb At A Glance - Vaillant geoTHERM VWS Installation Instructions Manual

Hide thumbs Also See for geoTHERM VWS:
Table of Contents

Advertisement

6 Electrical installation
6.5

Controller PCB at a glance

L
N
ZH
1
N
Fig. 6.6 Controller PCB
Key to Fig. 6.6
Upper connection terminals
1
ZH
External electric auxiliary heating
2
CP/SV1
External 3-port diverter valve for DHW loading
3
ZP
Circulation pump for hot water
4
SK2-P
VWS: cooling contact with cooling hydraulics
VWW: contactor, immersion pump
5
HK2-P
External (second) heating circuit pump
6
HK2
Actuation of 3-way mixer valve or 3-way diverter
valve (depending on hydraulic plan)
7
VF2
External flow sensor
8
RF1
Buffer cylinder base temperature sensor
9
VF1
Buffer cylinder head temperature sensor
10 BUS
eBUS
11
DCF / AF Outside temperature sensor + DCF signal
12 EVU
EVU contact (supply interruption, ripple control sig-
nal from power company)
open: compressor operation permitted
closed: compressor operation blocked
13 1xZP
Contact for non-recurring request for the circulation
pump, e. g. via external button
PCB components
14 eBUS/vrDIALOG
15 eBUS address rotary switch, set to "1" (factory setting)
16 Fuse T 4A/250 V for controller PCB
17 Check LED for power supply (lights green if OK)
18 T 4A/250 V fuse for brine pump
19 Monitoring of compressor phase sequence
30
1
2
3
4
5
Z u
A uf
N
L
N
L
N
L
N
L P /UV 1
ZP
SK 2 -P
HK 2 -P
2
3
4
5
L
N
L
N
L
N
L
N
L
32
31
30
29
28
6
7
8
Z u
A uf
N
1 2
1 2
1 2
HK2
VF2
RF1
VF1
S CH
6
7
8
A SB
2
1
L
N 2 1
L N
2 1
27
26
25
24 23
20 Plug for display (user interface)
21 Sensor connection plug 1
22 Sensor connection plug 2
Lower connection terminals
23 ASB Inrush current limiter
24 8
Compressor contactor
25 7
Pressostat safety chain
26 6
(not connected)
27 SCH Brine pressure switch (accessory) on modular terminal
(VWW: Flow switch)
28 5
Brine pump (VWS only)
29 4
Power supply, controller PCB
30 3
Heating circuit pump (on modular terminal)
31 2
Unused
32 1
Actuation of 3-way mixer valve, brine circuit (VWS only,
on modular terminal)
a
Installation instructions geoTHERM VWS/VWW 0020051574_01
9
10
11
12
13
- +
1 2
DCF O T AF
1 2
1 2
SP
BUS
DC F / AF
E VU
1xZP
Caution!
Risk of damage!
The following applies for external actua-
tors and actuators provided on the cus-
tomer side: I
= 2 A, U
max
The maximum current of all actuators/
consumers must not exceed 4 A at the
controller PCB.
14
15
16
17
18
19
20
21
22
= 230 V
max

Advertisement

Table of Contents
loading

This manual is also suitable for:

Geotherm vww

Table of Contents