5 Installation
Selection of the low loss header
The low loss header uncouples the boiler from the
heating system. A sufficiently large water volume is
constantly supplied through the boiler via the low loss
header in conjunction with the boiler pump. It acts as a
neutral point in the system and has minimal hydraulic
resistance, therefore the boiler pump does not affect
the circuit pumps and vice-versa.
A suitable WH type low loss header can be chosen from
Table 5.1.
Temperature difference of heating system
Output of heating
10 K
system
Stand-alone boiler
WH 160
Two cascade
WH 280
arrangement
Three cascade
WH 280
arrangement
Table 5.1 Selection of the low loss header
No electrical accessories are required in order to use a
low loss header. Simple systems can be connected
directly inside the electronic box.
Model
Article-
Connection
number
Sizes
1
WH 95
306721
2" BSP (f)
WH 160
306726
DN65
WH 280 306725
DN80
Table 5.2 Low loss headers dimensions
All dimensions in mm
* = distance between flanges
14
15 K
20 K
WH 95
WH 95
WH 160
WH 95
WH 280
WH 160
Header
Header
Total
width
depth
height
A
B
C
155
155
750
520*
120
1350
600*
160
1390
Insulation
To boiler
To heating
dimensions
circuit
D
155/155
470
220/220
900
260/260
930
Installation and maintenance instructions ecoTEC 0020029173_01
Height from
Maximum
floor
volume flow
E
F
540
n/a
900
300
930
300
3
m
/hr
8
12
21.5