Baxi Solarflo User Manual page 7

Evacuated tube collector
Table of Contents

Advertisement

Indication
max
65ºC
dT max
7 K
dT min
3 K
min
100
min
40ºC
dT
10K
min
(1)
00:00
max
(1)
23:59
min
(2)
00:00
max
(2)
23:59
min
(3)
00:00
max
(3)
23:59
min
(4)
00:00
max
(4)
23:59
13:21
* Temperature lag between switch on and switch off
© Baxi Heating UK Ltd 2011
Press
or
up or down to the required sub function.
The icon will flash, press
select the function. Reset by pressing
or
for
increase/decrease values. Press
and
appears,
ok?
press
to confirm and
disappears.
Description
Storage 1/2:
Maximum temperature
Storage 1/2: Hysteresis (dT on) *
Storage 1/2: Hysteresis (dT off) *
Setting the speed control of the pump
100% = speed control off
2
Temperature start for the function
heating
Hysteresis heating
Start time 1
for the independent controller
Stop time 1
for the independent controller
Start time 2
for the independent controller
Stop time 2
for the independent controller
Start time 3
for the independent controller
Stop time 3
for the independent controller
Start time 4
for time controlled circulation
Stop time 4
for time controlled circulation
Clock
to scroll
4.0
User Controls
to
4.3
Menu "Programming"
All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
ok?
invalidate the warranty.
Value range
Defaults
15..65ºC
65ºC
3..40 K
7 K
2..35 K
3 K
30%..100%
100%
20..90ºC
40ºC
1..30K
10K
0:00...
00:00
23.59
0:00...
23:59
23:59
0:00...
00:00
23.59
0:00...
23:59
23:59
0:00...
00:00
23.59
0:00...
23:59
23:59
0:00...
00:00
23:59
0:00...
23:59
23:59
0:00...23.59
12:00
*