Uni- Fit Thru-the-Wall Series Service and Parts Manual Thru-the-Wall Series 115 Volts US08C10 US10C10 US12C10 230 Volts US10C30 US12C30 US14C30 Unifit Cool Svc Parts 2010 (05/10) Unifit. Cool (03/07)
SERVICE MANUAL This parts etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit. 1.1 SAFETY PRECAUTIONS 1.
1.3 SPECIFICATIONS MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR...
Page 4
MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR COMPRESSOR...
Page 5
MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR COMPRESSOR...
Page 6
MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR COMPRESSOR...
Page 7
MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR COMPRESSOR...
Page 8
MODELS ITEMS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL AIR DIRECTION CONTROL CONSTRUCTION PROTECTOR COMPRESSOR...
This feature is best used in conjunction with the FAN ONLY position. CAUTION When the air conditioner has been operating in the cooling and is turned off or set to the fan only position, wait at least 3 minutes before resetting to the cooling operation again.
2. DISASSEMBLY INSTRUCTIONS — Prior to disassembling the unit, make sure that the POWER is off and the power cord is unplugged from the wall receptacle. 2.1 MECHANICAL PARTS 2.1.1 FRONT GRILLE 1. Open the inlet grille downward. 2. Remove the screw which fastens the front grille. 3.
2.2 AIR HANDLING PARTS 2.2.1 ORIFICE, AND TURBO FAN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the 2 screws which fasten the evaporator at the left side and the right side. (See Fig.
2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Fig. 9) 3. Re-install the components by referring to the removal procedures, above. 2.3 ELECTRICAL PARTS 2.3.1 MOTOR 1. Remove the cabinet. (Refer to section 2.1.2) 2.
2.3.4 POWER CORD 1. Remove the control box. (Refer to section 2.1.3) 2. Unfold the control box. (Refer to section 2.3.3) 3. Disconnect the grounding screw from the Base pan. 4. Disconnect 2 receptacles. 5. Remove a screw which fastens the clip cord. 6.
2.4 REFRIGERATION CYCLE CAUTION Discharge the refrigerant system using a Freon Recovery System. Install a valve for the recovery, before venting the Freon, remove the valve when finished. 2.4.1 CONDENSER 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the brace. (Refer to section 2.2.1) 3.
Page 15
NOTES — Replacement of the refrigeration cycle. 1. When replacing refrigeration components, be sure to discharge the refrigerant system using a Freon recovery System. Install a valve for the recovery, before venting the Freon, remove the valve when finished. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
Page 16
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve. Figure 17A-Pulling Vacuum Figure 17B-Charging —16—...
Refer to Fig. 18 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle. EVAPORATOR COILS COOLED LIQUID PRESSURE DROP " ROOM AIR CONDITIONER CYCLE OF REFRIGERATION SUCTION LINE COMPLETE LIQUID COOL LOW PRESSURE VAPOR BOIL OFF POINT ROOM AIR HEAT LOAD...
3.3 TROUBLESHOOTING GUIDE In general, possible trouble is classified in two causes. One is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and/or improper application. Unit is running but cooling is ineffective Check cold air circulation for smooth flow.
Page 19
Check power source. Check control switch setting. Only compressor fails to start. Drop in power voltage. Defective compressor capacitor. Check capacitor. Replacement. Irregular motor resistance ( ) Irregular motor insulation ( ) Replacement of compressor (Motor damaged) Fails to Start Improper thermostat setting Loose terminal connection.
Page 20
Fan motor will not run. No power Wire disconnected or connection loose Capacitor (Discharge capacitor before testing.) Will not rotate Fan motor runs Cycles on overload. intermittently Fan motor noise. Grommets Turbo fan Loose set screw Worn bearings Check voltage at outlet. Correct if none. Connect wire.
Compressor Overload ROOM AIR CONDITIONER VOLTAGE LIMITS Check voltage. See the limits on the preceding. page. If not within limits, call an electrician. Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace.
Page 22
COMPLAINT Compressor cycles Voltage on overload. Overload Fan motor Condenser air flow restriction Condenser fins (damaged) Capacitor Wiring Refrigerating system Insufficient cooling or Air filter heating Exhaust damper door Unit undersized Excessive noise. Blower or fan Copper tubing CAUSE Check the voltage. See the limits on the preced- ing page.
Page 31
FRIEDRICH AIR CONDITIONING CO. Visit our web site at www.friedrich.com Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4480 P/NO.:3828A20294U Printed in the U.S.A Unifit Cool Svc Parts 2010 (05/10)
Need help?
Do you have a question about the Uni-Fit US08C10 and is the answer not in the manual?