TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Installer
Setup
Installer Setup
Number
Name
0600
Heat Temperature
Range Stops
0610
Cool Temperature
Range Stops
0640
Clock Format
0650
Extended Fan-on
time Heat
0660
Extended Fan-on
time Cool
0670
Keypad Lockout
0680
Temperature
Control Heat
0685
Recovery Heat
Ramp Rate
0690
Temperature
Control Cool
0695
Recovery Cool
Ramp Rate
0700
Temperature
Display Offset
0710
Restore Factory
Defaults
INSTALLER TESTS
Test 1
Installer Test
Cool
Test 2
Installer Test
Fan
Test 3
Installer Test
Heat
Test 4
Installer Test
Auxiliary Heat
Test 8
Installer Test
TOD/Economizer
NOTE: Press the Done key to exit the Installer System Test.
62-0221—05
Table 4. Installer Setup Menu. (Continued)
Default
Setting
All Settings
90
40 to 90°F (4 to 32°C)
50
50 to 99°F (10 to 37°C)
12
12—12 Hour
24—24 Hour
0
0—Off
90—90 seconds
0
0—Off
40—40 seconds
0
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
2
1—Less Aggressive
2—Standard
3—More Aggressive
5
0-20°F/hour
2
1—Less Aggressive
2—Standard
3—More Aggressive
3
0-20°F/hour
0
-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
0
0—No
1—Yes
0
0—Off
1—Cool Stage 1
2—Cool Stage 2
0
0—Off
1—Fan On
0
0—Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
0
0—Auxiliary Heat Off
1—Auxiliary Heat On
0
0—TOD/Economizer Off
1—TOD/Economizer On
Only shown if system has heat stages (ISU 0170).
Only shown if system has cool stages (ISU 0170).
Not displayed with cool-only systems (ISU 0170)
or with fan set to system control (ISU 0180 at 0).
Only shown for systems with cool stages (see ISU
0170).
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
Only shown if system has heat stages (ISU 0170).
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
Only shown if system has heat stages (ISU 0170).
0 disables ramped recovery (step setpoint change
at period start time).
Only shown if system has cool stages (ISU 0170).
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
Only shown if system has cool stages (ISU 0170).
0 disables ramped recovery (step setpoint change
at period start time).
This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).
Resets all ISU parameters to default values and
resets the schedule to default (see Table 5).
Retains only calendar settings and time.
12