NETWORKING

ADAPTAIRE DEFAULT SETTINGS

MUA-SVP01A-EN • Direct-Fired Indoor and Outdoor Units
AdaptAire is adaptable to a variety of different network architectures and
protocols. Each controller has built-in protocol translation and can be configured
for operation on ARCnet156 or EIA-485 communication networks. See Appendix
IV for specific controller specifications.
The AdaptAire system can be connected to most existing building automation
systems. Some systems may require the use of special controllers and network
communication devices. See Appendix I for Device Parameters and Cache Setup
information.
The following is a list of AdaptAire DDC controller defaults. These are the default
operating parameters set at the factory prior to shipment.
Table 1.
Default settings
ITEM
Unit Network Address
Unit Operating Mode
Time Clock Schedule
Heating/Cooling Operating
Mode
Damper Operating Mode
Fuel Selection
Heating Night Setback
Cooling Night Setback
Room Temperature Setpoint
Freezestat
Outside Air Economizer
Setpoint
Minimum Discharge
Temperature Setpoint
Maximum Discharge
Temperature Setpoint
Mixed Air Temperature
Setpoint
Building Pressure Setpoint
Manual Damper Position
Setpoint
Minimum Ventilation
Setpoint
User PID Select
High Input Value
DEFAULT
002 binary dips
OFF
None
Heating
Manual
Natural Gas
55°F
100°F
65°F
45°F
65°F
55°F
100°F
50°F
0" W. C.
20% Outside Air
20% Outside Air
Direct Acting
0
RANGE
000 – 255 binary dips
OFF – MANUAL - AUTO
4 Daily - 12 Holiday - 2
Override schedules
HEATING - COOLING
MANUAL - BUILDING
PRESS - MIXED AIR
TEMP
NATURAL - PROPANE
40°F - 80°F
75°F - 120°F
55°F - 90°F
35°F - 50°F
40°F - 80°F
40°F - 130°F
55°F - 130°F
30°F - 90°F
-0.05" - +0.05" W. C.
0% - 100%
0% - 100%
DIRECT -REVERSE
-9999.99 – 99999.99
3