I/O Zone 583 Controller Specifications
–
LED indication
•
3 Analog Outputs
–
0 - 10 VDC
OUTPUT ASSIGNMENTS - ANALOG
AO1 Burner firing rate (to signal conditioner) 0 - 10 VDC
AO2 RA or Mixing Damper Control/ User Configured 0 - 10VDC
AO3 Unassigned
OUTPUT ASSIGNMENTS - DIGITAL
DO1 Unit Enable
DO2 Burner Enable
DO3 Cooling Enable
DO4 Alarm
DO5 Pilot to Main Flame Sensor Changeover Switch
INPUT ASSIGNMENTS - UNIVERSAL
IN1 Pressure Transducer for Building Pressure Control or User Configured
IN2 Pressure Transducer for Flow Station
IN3 Multiplexed
•
100% Outside Air/100% Output
•
Flame Failure Alarm
•
Safety Circuit Status
•
Manual/Mixed Air Dmpr Control
IN4 Multiplexed
•
Auxiliary Unit Enable
•
Clogged Filter
•
Fan Status
•
Burner Status
IN5 Outside Air sensor
IN6 Discharge Air sensor
IN7 Unit Enable/Remote Setpoint
IN8 Damper Control
RNET MRT-Pro or Room Air sensor