Water Piping Connections
All CDHF units, "A" and later design
sequences, use grooved-pipe
connections. (See Table 5). These are
cut-groove end NSP (Victaulic
pipe connection .
Flanged connections for 300 PSI
waterboxes use welded flanges.
Piping joined using grooved type
couplings, like all types of piping
systems, requires proper support to
carry the weight of pipes and
equipment.
The support methods used must
eliminate undue stresses on joints,
piping and other components; allow
movement where required, and
provide for any other special
requirements (i.e., drainage, etc.).
CDHF-SVN01B-EN
Water Piping
Table 3 – Evaporator Water Piping
Connection Sizes –
CDHF and CDHG
Evaporator
Units
Size
Range
1250-2000
1250-2150
2100-2500
3000
3500
Note:
EVSZ = Evaporator Shell Size;
D = Duplex
Table 5 – Water Piping Connection Components
Unit Model
CDHF or CDHG
-style)
CDHF or CDHG
Figure 15 – Typical Grooved Pipe Connection
Shell
Connection
Size
Size
EVSZ
1 Pass
210D
16"
210D
16"
250D
16"
250M
18"
250X
18"
Water Box
Connection
Type
150 psig
Victaulic
Customer provided
Victaulic Coupling
Flanged
Trane provided
Victaulic-to-Flange
Adapter
Table 4 – CondenserWater Piping
Connection Sizes –
CDHF and CDHG
Condenser
Units
Shell
Size
Size
Range
CDSZ
1250-2000
210D
1250-2150
210D
2100-2500
250D
3000
250M
3500
250X
Note:
CDSZ = Condenser Shell Size;
D = Duplex
Water Box Design Pressure
300 psig
Customer provided
Victaulic Coupling
Trane Provided
Welded on
Flange
Connection
Size
1 Pass
16"
16"
16"
20"
20"
29