FortiGate-5050 chassis. The most recent versions of this and all FortiGate-5000 series documents are available from the page of the Fortinet Technical Documentation Visit http://support.fortinet.com to register your FortiGate-5050-R chassis. By registering you can receive product updates, technical support, and FortiGuard services.
ESD connector such as the ESD sockets provided on FortiGate-5000 series chassis. • Make sure all FortiGate-5000 series components have reliable grounding. Fortinet recommends direct connections to the building ground. •...
Using FortiSwitch-5003A and FortiSwitch-5003 boards for backplane communication... 26 For more information... 27 Fortinet documentation ... 27 Fortinet Tools and Documentation CD ... 27 Fortinet Knowledge Center ... 27 Comments on Fortinet technical documentation ... 27 Customer service and technical support... 27 Register your Fortinet product ...
This chapter describes the FortiGate-5050 chassis and includes the following sections: • FortiGate-5050 front panel • FortiGate-5050 back panel • Physical description of the FortiGate-5050 chassis • FortiGate-5050 shelf managers • FortiGate-5050 shelf alarm panel • Shelf manager command line interface (CLI) FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
FortiGate-5050 chassis “FortiGate-5050 shelf managers” on STA IPM STA IPM Hot-swappable STA IPM cooling fan tray POWER Power LED 5000SM 10/100 SERIAL link/Act 10/100 link/Act ESD socket Primary Shelf Manager (SMC 1) FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
The RTM slots are available for FortiGate-5000 RTM modules such as the FortiGate-RTM-XB2 module. When the FortiGate-5050 chassis is shipped, these slots are covered by RTM slot filler panels. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback shows the back of a FortiGate-5050 chassis. The FortiGate-5050 chassis back INPUT A...
The alarm LED reset button (RESET) on the shelf alarm panel activates the Alarm Cutoff (ACO) state. When ACO is activated, the active alarm LEDs blink and all of the alarm relays are deactivated. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback Reset Hot Swap...
Page 10
The external dry relay Telco alarm interface (48VDC) provides Telco form-c relay connections for minor, major and critical power faults. The cable required to connect to the alarm interface is not supplied by Fortinet. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ •...
When the ACO state is activated, active alarm LEDs blink and all of the alarm relays are deactivated. The alarm reset button activates the ACO state but does not clear the alarm completely. Figure 6: The telco alarm connector (DB-15 male) FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback 5050SAP Buffer I²C-Switch I²C-Switch...
AMINC MinorAlarm - NC AMINCOM MinorAlarm - COM AMANO MajorAlarm - NO AMANC MajorAlarm - NC AMACOM MajorAlarm - COM APRCO PwrAlarm - NO APRCOM PwrAlarm - COM Shelf-GND Shelf Ground FortiGate-5050 chassis FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
Page 13
SERIAL To connect to the shelf manager CLI using a shelf alarm panel serial port 1 Connect the Fortinet console cable to the shelf alarm panel Serial 1 or Serial 2 port (see 2 Connect the Fortinet console cable to your PC or other device RS-232 console port.
Page 14
Change the order of FRU Activation and Power Descriptors instead of <addr> <fru_id> user may use: PwrReorder <addr1> <fru_id1> before/after <addr2> <fru_id2> board <N> shm <N> power_supply <N> (valid in 2.x systems only) fan_tray <N> FortiGate-5050 chassis FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
The FortiGate-5050 chassis is designed to be installed in a data center or similar location that has available -48VDC power (also called battery power). Fortinet expects that most FortiGate-5050 customers will be installing their FortiGate equipment in a data center or similar location that is already equipped with a -48VDC power system that provides power to existing networking or telecom equipment.
Page 16
9 Re-attach the protection plate to the FortiGate-5050 power input connector. Data Center -48VDC connector -48V (-DC in) black to Data Center -48VDC INPUT A -48V RTN (-DC IN) Positive (-DC in) (black) (RTN) (red) Figure FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
Selecting the power supplies and power converter trays that you need for your FortiGate-5050 configuration • Connecting a FortiGate-5050 chassis to the FortiGate-5053 power converter tray FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback Power connection and configuration Figure 2 on page 7). This connector must be connected...
LED lights. RTN(RED) -48V(BL ACK) (RTN) -48V (RED) (BLACK) DC out Figure 10) provides AC Power LED DC Power Slot 1 Figure 11) includes one DC power 100-240VAC 1 AC in FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
FortiGate-5050 chassis. This section provides guidelines only. Actual requirements may vary depending on your installation requirements. Contact Fortinet Technical Support if you need more information. The FortiGate-5053 power converter tray contains space for up to three FortiGate-5020/5050 power supplies.
Page 20
10/100 10/100 link/Act SERIAL SERIAL link/Act 10/100 10/100 link/Act link/Act CONSOLE STA IPM CONSOLE STA IPM CONSOLE STA IPM POWER 5000SM 5050SAP 5000SM 10/100 10/100 link/Act SERIAL SERIAL link/Act 10/100 10/100 link/Act link/Act FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
(the left connector) to the terminal on the FortiGate-5050 power input connector labelled RTN. Caution: The FortiGate-5053 power converter tray should not be connected to AC power until specified in the following procedure. Figure 16). FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
Page 23
FortiGate-5050 chassis. This photograph also shows the clear back cover of the FortiGate-5053 installed. You should install this cover using the mounting hardware provided. Install the cover after connecting the power but before turning the power on. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback converter tray (RTN)
9). None of the LEDs on the shelf alarm panel (SAP) should Figure 4 on page 10). “To connect the FortiGate-5050 chassis to 18). When the FortiGate-5053 power Figure 2 on Figure 1 on FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
FortiGate-5000 series boards or with air baffle slot fillers. Air baffle slot fillers are similar to blank FortiGate-5000 boards and are required for proper cooling air flow. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback “Power connection and configuration” on page Note: Mount the FortiGate chassis before installing the FortiGate-5000 series modules.
As well the removable PEM terminal block covers must be installed over the power connectors on the back of the chassis. FortiGate-5050 hardware procedures Guide. FortiGate-5050-R Chassis Guide 01-30000-87717-20090108 http://docs.fortinet.com/ • Feedback...
Fortinet documentation is available from the Fortinet Tools and Documentation CD shipped with your Fortinet product. The documents on this CD are current for your product at shipping time. For the latest versions of all Fortinet documentation see the Fortinet Technical Documentation web site at http://docs.forticare.com.