Download Print this page

Troubleshooting - Honeywell CSP-C Installation Instructions

Solid core and split core adjustable current “status” switches

Advertisement

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT "STATUS" SWITCHES
Calibration of Adjustable Trip Point
The adjustable current switch has an operating range of
0-200 Amps or 0-250 Amps. Do not exceed! The
adjustable current switch comes with its fifteen-turn
adjustable potentiometer set counter-clockwise
its maximum position. The adjustable current switch can
monitor Under load, Normal load and Overload
conditions, depending on how it's set. The procedure
below is for Normal load condition for part numbers
CSS-O-A300-001 and CSS-O-A200-001.

TROUBLESHOOTING

Problem
Red LED is on but the
current switch didn't activate.
Red LED didn't turn on and
the current switch didn't
activate
Sensor doesn't switch at all,
regardless of current level.
Product Number
CSS-O-A300-001
Greater than 1 Meg ohms
CSS-O-A200-001
Greater than 1 Meg ohms
CSS-C-A300-001
Greater than 1 Meg ohms
CSP-O-A300-001
Greater than 1 Meg ohms
CSP-O-A200-001
Greater than 1 Meg ohms
CSP-C-A300-001
Greater than 1 Meg ohms
CSP-C-A200-001
Greater than 1 Meg ohms
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
62-0242—01 C.H. Rev. 06-07
Disconnect the wires from the current switch output. Measure the resistance across the
contacts with an Ohmmeter. See Table 2 below for resistance readings for a good unit.
Verify that the conductor you are monitoring is above the adjustable trip point. If the
sensor is monitoring less than the adjustable trip point, looping the wire may be
required. See Fig. 3.
Adjustment potentiometer is probably set to its maximum or minimum position. Turn the
potentiometer clockwise all the way and verify if the LED switches from red to green.
Table 2. Resistance Readings For Good Unit.
Resistance if switch is open
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
Normal loads
With power on and the adjustable current switch on the
proper range, turn the fifteen-turn adjustment
potentiometer clockwise
to
and stop immediately. The adjustment switch is now
tripped. The adjustable current switch Hysteresis (Dead
Band) is 10% of the trip point typically.
Solution
Resistance if switch is closed
Approximately 2 ohms
Approximately 2 ohms
Approximately 12 ohms
Approximately 2 ohms
Approximately 2 ohms
Approximately 12 ohms
Approximately 12 ohms
until the red LED turns on

Advertisement

loading

This manual is also suitable for:

Csp-oCss-cCss-o