Honeywell VISIONPRO TB8220U Installation Instructions Manual page 10

Commercial programmable thermostat
Hide thumbs Also See for VISIONPRO TB8220U:
Table of Contents

Advertisement

TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
Installer
Setup
Installer Setup
Number
Name
0170
System Selection
0175
TOD/Economizer
output (terminal A)
0180
Heat Fan Operation 0
0185
Pre-occupancy
Purge Duration
0190
Reversing Valve
O/B
0220
Cycles Per Hour
(CPH) for first stage
compressor
0230
CPH for second
stage compressor
0240
CPH for first stage
conventional heat
0250
CPH for second
stage conventional
heat
0260
CPH for third Stage
Heat
0270
CPH for Auxiliary
Heat
0280
Continuous
Backlight
0300
Changeover
0310
Deadband
0320
Temperature
Indication Scale
0330
Daylight Saving
62-3070—07
Table 4. Installer Setup Menu. (Continued)
Default
Setting
All Settings
8
1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP (Aux. Heat)
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP (Aux.
Heat)
0
0—Unused
1—TOD
2—Economizer
0—Fossil
1—Electric
0
0—no duration
1—one hour
2—two hours
3—three hours
0
0—O (O/B On Cool)
1—B (O/B On Heat)
3
1-6
3
1-6
5
1-12
9
1-12
9
1-12
9
1-12
0
0—No
1—Yes
1
0—Manual
1—Auto
3°F
2 (1.5)—2°F (1.5°C)
(2°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
0
0—°F
1—°C
2
0—Disabled
1—Enabled (US 1987)
2—Enable (US 2007)
3—Enabled (Europe)
To use the Emergency Heat button, select setting
#7 or #12. See Fig. 16 or 17 for auxiliary heat
wiring.
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and de-
energizes A during Unoccupied.
Only shown for conventional system with heat
stages and fan capability selected. If heat pump is
selected, fan defaults to electric.
Shown only if system has fan and schedule
programmable.
Pre-occupancy purge enabled by nonzero duration
(and sends economizer to minimum position).
Only shown with heat pump system selected.
Only shown for system with cool stages. Selection
in this stage changes default CPH of second stage
cool.
Only shown if two stages of cool selected.
Only shown if system is conventional with heat
stages.
Selection in this stage changes default CPH of
second stage heat.
Only shown with at least two stages conventional
heat or 2H/1C heat pump selected.
Only shown if 3H/2C heat pump is selected.
Only shown if multi-stage heat pump is selected
(heat pump with more heat than cool stages).
Always shown. If AC power not present the option
is overridden and normal backlight operation
occurs.
Only shown if system has both heat and cool
stages.
Only shown if Automatic Changeover Selected
10