COMBAT
®
UHA U
H
NIT
EATER
Figure 1: Installation Clearances and Clearances to Combustibles
* Recommended mounting height varies with heater input.
Heaters may be mounted at a higher level if destratification
fans are installed.
Note: Venting directly from top of heater not applicable
on Models 150 - 400.
The heater must always be installed at least 6' (2 m) above the floor.
The vent pipe must have clearance from combustibles by 2" (5 cm).
If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.
4
I
O
NSTALLATION
PERATION AND
S
M
ERVICE
ANUAL
Clearance to Vent: 2" (5 cm)
**31" (79 cm) minimum is necessary
for servicing.