Gas Valves - Amana VR8205 Installation Instructions Manual

Gas fired warm air furnace
Table of Contents

Advertisement

5. Open Limit Control (Primary or Auxiliary)
An open limit control can be caused by a low condi-
tioned air flow due to dirty filter or resistance in duct
work, a faulty blower, a blower speed set too low, or a
faulty limit.
When the limit control opens, the induced draft and air
circulation blowers are turned on. The induced draft
blower will remain on for the first fifteen seconds of this
period. The air circulation blower will remain on until
the limit control is closed. The diagnostic light code for
this is four short flashes followed by a pause.
6. Open Rollout Control
An open rollout control is can be caused by insufficient
combustion air, a restricted flue passage, or a re-
stricted heat exchanger.
The opening of the rollout control signals the air circu-
lation blower and the induced draft blower to turn on.
The air circulation blower will remain on until the limit
is manually reset. The induced draft blower will remain
on for the first fifteen seconds of this period. The
diagnostic light code for this is five short flashes
followed by a pause.
7. Flame Sensed with No Call for Heat
If the control senses a flame when the gas valve is de-
energized, it will run the air circulation blower and the
induced draft blower continuously. The diagnostic light
code for this is continuous light flashing. Probable
cause is miswiring.
OPERATING INSTRUCTIONS
1. Close the manual gas valve external to the furnace.
2. Turn off the electrical power supply to the furnace.
3. Set room thermostat to lowest possible setting.
4. Remove the door on the front of the furnace.
Note: This furnace is equipped with an ignition device to
automatically light the burners. Do not try to light burners
by hand.
5. Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222: Turn the gas
control knob clockwise
Note: The knob should turn easily. Do not use exces-
sive force.
White Rodgers Model 36E22: Push the switch to the
OFF position.
6. Wait five minutes to clear out any gas. Then smell for
gas, including near the floor.
7. If gas can be smelled following the five minute waiting
period in Step 6, immediately follow the instructions on
Page 2 of this manual. If you do not smell gas after five
minutes:
Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222: Turn the gas
control knob counterclockwise
tion. The knob should turn easily. Do not use exces-
sive force.
White Rodgers Model 36E22: Push the switch to the
ON position.
10. Turn on the electrical power supply to the furnace.
11. Set the room thermostat to the desired temperature.
NOTE: There is an approximate 20 second delay between
thermostat energizing and burner firing.
to the OFF position.
to the ON posi-
24
8. Replace the door on the front of the furnace.
9. Open the manual gas valve external to the furnace.

Gas Valves

Figure 36
Honeywell Model VR-8205
Figure 37
White Rodgers Model 36E36
Gas Control
Valve Lever
(In ON Position)
INLET
Inlet Pressure Tap
Figure 38
Robertshaw Model 7222
Outlet Pressure Tap
(Side of Valve)
OUTLET
Pressure Regulator
Adjustment (Under
Cap Screw)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gui seriesGci series

Table of Contents