T8511G,R MICROELECTRONIC HEAT PUMP THERMOSTATS
Installer Setup
Number
(Press i key
to change)
Select
Extended fan
19
operation in
heating
Extended fan
20
operation in
cooling
Not used
21 thru 23
Outdoor
24
temperature
display
Not used
25 thru 28
O/B terminal
29
energized in
heating or
cooling
Not used
30 thru 32
Minimum off
33
time for the
compressor
34
Heating
setpoint range
stop
Cooling
35
setpoint range
stop
System On
36
display
Temperature
37
display
adjustment
a
T8511G is 48°F.
69-0927—4
Table 2. Thermostat Installer Setup Options (Continued).
Factory-Setting
Display
Description
00
No extended fan
operation after the call
for heat ends
00
No extended fan
operation after the call
for cool ends
00
No outdoor temperature
is displayed
00
O/B terminal is
energized for reversing
valve in cooling
05
5 minute minimum off
time for the compressor
90
Heating setpoint can be
set no higher than 90°F
a
45
Cooling setpoint can be
set no lower than 45°F
00
LCD On symbol is
displayed when system
is energized
00
No difference in
displayed temperature
and actual room
temperature
Other Choices
(Press
Display
01
Fan operation is extended
90 seconds after the call for
heat ends
01
Fan operation is extended
90 seconds after the call for
cool ends
01
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate.
01
O/B terminal is energized for
reversing valve in heating
00, 01,
Minimum number of minutes
02, 03
(0 thru 5) the compressor will
or 04
be off between calls for the
compressor
40 thru
Number can be set
90
anywhere between 40 and
90 in 1°F increments
a
45
thru
Number can be set
a
99
anywhere between 45
99 in 1°F increments
01
Display is disabled, usually
set for 01 for a zoned system
01—Display adjusts to 1°F
-3 thru
higher than actual room
03
temperature
02—Display adjusts to 2°F
higher than actual room
temperature
03—Display adjusts to 3°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature
6
or
key to change)
Description
a
and
Actual
Setting