Removal And Replacement Of Water Regulating Valve - Water Cooled Model Only - Hoshizaki KML-451MAH Service Manual

Low-profile modular crescent cuber
Hide thumbs Also See for KML-451MAH:
Table of Contents

Advertisement

8) Remove the drier, then place the new drier in position.
9) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
10) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
11) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled
models, see the nameplate for the required refrigerant charge. For remote air-cooled
models, see the rating label inside the icemaker.
12) Replace the removed parts in the reverse order of which they were removed.
13) Replace the top insulation and the panels in their correct positions.
14) Turn on the power supply.
F. Removal and Replacement of Water Regulating Valve -
Water Cooled Model Only
Always install a new drier every time the sealed refrigeration system is opened.
Do not replace the drier until after all other repair or replacement has been
made.
1) Turn off the power supply.
2) Close the water supply line shut-off valve.
3) Remove the panels.
4) Recover the refrigerant and store it in an approved container.
5) Disconnect the capillary tube at the condenser outlet.
6) Disconnect the flare-connections of the valve.
7) Remove the screws and the valve from the bracket.
8) Install the new valve.
9) Remove the drier, then place the new drier in position.
10) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
11) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
12) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
13) Connect the flare-connections.
14) Open the water supply line shut-off valve.
15) Check for water leaks.
16) Replace the panels in their correct positions.
17) Turn on the power supply.
IMPORTANT
38

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kml-451mwh

Table of Contents