Honeywell McDonald’s HEMS II Operation Manual page 9

Table of Contents

Advertisement

This area of Home Page shows the following:
1.
Current electrical peak demand and current electrical (KWH) consumption for the current month and
current year. By touching or clicking on any CYAN colored area you will be directed to a trend log of
accumulated electrical data. See page 18 of this document for more information on this.
2.
Current electrical demand set point. See page 19 of this document for more information this.
3.
Energy Demand Limiting: When active the box will say Active and the background will be RED. When
Inactive the box will say Inactive and the background will be YELLOW. When Active the temperature set
points for all HVAC Units will be automatically raised 3°F (when in cooling mode) or lowered 3°F (when in
heating mode). HVAC Units automatically switch between Cooling/Heating modes to maintain room
temperatures. Active condition exists when current electrical demand is within 2.5% of electrical demand set
point.
4.
By touching or clicking on Electrical icon you will be directed to another page for set point adjustments. See
page 19 of this document for more information on this.
Home Page – continued
McDonald's HEMS II page 9