CHAPTER6
DEVICENET COMMUNICATION FUNCTION
SJ-DN2 to Master: Instance101 (P047: 101)
Byte
Bit7
Input
0
Terminal
3 State
1
2
3
4
5
6
Ref From
7
Net
Data
Running1(Fwd)
Running2(Rev)
Faulted
At Reference
Input Terminal 1 State
Input Terminal 2 State
Input Terminal 3 State
Input Terminal 4 State
Input Terminal 5 State
Input Terminal 6 State
Input Terminal 7 State
Input Terminal 8 State
Forward Terminal State
Drive Status
Speed Actual
Bit6
Bit5
Input
Input
Terminal
Terminal
2 State
1 State
Forward
Ctrl From
Terminal
Net
state
It indicates inverter's running condition.
0:Stop / During reverse run 1:During forward run
It indicates inverter's running condition.
0:Stop / During forward run 1:During reverse run
It indicates the inverter is in a fault detecting state.
0:Normal
1:During detecting fault state
It indicates arrival frequency detecting state for the inverter.
0:During stop / During accelerate or decelerate
1:Arrival frequency
0: (opened) 1: Input terminal 1 and common are closed.
0: (opened) 1: Input terminal 2 and common are closed.
0: (opened) 1: Input terminal 3 and common are closed.
0: (opened) 1: Input terminal 4 and common are closed.
0: (opened) 1: Input terminal 5 and common are closed.
0: (opened) 1: Input terminal 6 and common are closed.
0: (opened) 1: Input terminal 7 and common are closed.
0: (opened) 1: Input terminal 8 and common are closed.
0: (opened) 1: Forward terminal (FW) and common are closed.
It indicates the inverter condition.
00:The inverter is stopping.
01:The inverter is running.
02:The inverter is in jogging mode.
03:The inverter's output is stopped and the motor is free running (coasting).
04:The inverter is executing DC braking.
This includes the DC braking wait time.
05:The inverter is trying to restart with frequency matching.
Command b001 is set to "3".
06:Stop output at instantaneous power failure.
07:The inverter is trying to restart with frequency matching.
Command b001 is set to "2".
08:The inverter is waiting before it runs on motor again to restart with
frequency matching (by setting b001, b088, C103).
This waiting time is as setting value command b003.
10:The inverter is in a trip condition.
11:The inverter is in under-voltage condition.
It indicates the inverter's output frequency monitor.
Monitor range:0.00 to 400.00(Hz), Resolution: 0.01(Hz), Magnification:100
times, Receiving data:0 to 9C4O(Hex)
Bit4
Bit3
At
-
Reference
Drive Status
Speed Actual (Low Byte)
Speed Actual (High Byte)
Output current (Low Byte)
Output current (High Byte)
Trip cause
Input
Input
Terminal
Terminal
8 State
7 State
Contents
16
Bit2
Bit1
Running2
Faulted
(Rev)
Input
Input
Terminal
Terminal
6 State
5 State
Bit0
Running1
(Fwd)
Input
Terminal
4 State