Kenmore ELITE 153.331000 Use & Care Manual page 48

Hybrid gas water heater 25 u.s. gal (94.6 litres)
Hide thumbs Also See for ELITE 153.331000:
Table of Contents

Advertisement

If an error code is displayed, or odd behavior of the unit occurs, the first corrective action should be to "Cycle the
Power": Unplug the 120Vac power cord and after 5 seconds plug it in again. If this doesn't clear the fault, proceed with
the "Remedy" in the following table (Table 4). The remedies for each fault code are put in logical order, so proceed one
by one, starting with #1.
If wire harness checking is required, examine the integrity of wires themselves, the connector housings, the integrity of
the terminals as well as condition of the crimps.
E01, E02
E03, E04,
E05, E06
E07
E08
E09
El0
Ell
Invalid Rated
KBtu/Model Type.
Main Valve Relay
Out Of Sequence.
Flame Detected.
ECO Switch is
open.
High Temperature
Switch open.
120Vac too high.
120Vac too low.
Control detects that the
configuration selected is not
defined or the configuration
has never been set.
Control detects that a relay
used to enable the Main
Valve has failed in either the
open or closed position.
Flame detected when no
flame was expected.
Control detects that the
ECO Switch is open,
preventing power to the
Main Valve.
Control detects that the High
Temperature Switch is open,
preventing power to the
Main Valve.
120Vac > Overvoltage Limit.
120Vac < Undervoltage
Limit.
Continuous
Soft
Soft
Continuous
Continuous
Auto Reset
Change the Control Board.
Change the Control Board.
1. Check the Flame Sensor.
2. Check the flame wire harness.
3. Change the Control Board.
1. Check inlet water filter.
2. Measure the water temperature.
ECO Switch open temperature
is 85+5°C (185+14°F) and close
temperature is 65+5°C (149+14°F).
3. Check the ECO Switch.
4. Check the ECO wire harness.
5. Change the Control Board.
1. Measure the exhaust gas
temperature. High Temperature
Switch open temperature
is
74+2.8°C (165+5°F) and close
temperature is 57+2.8°C (135+5°F).
2. Check the switch.
3. Check the High Temperature Switch
wire harness.
4. Change the Control Board.
Nominal voltage is 120Vac.
Overvoltage limit is 132Vac,
Undervoltage limit is 102Vac.
1. Check the power cord.
2. Check the wall outlet.
3. Measure the voltage at the board
connector J7 between pin1 and pin
3. If the voltage is between limits,
change the Control Board.
TABLE 4
48
Part Number 320169-001
dRaFt Jun 9 130