GE AZ75W18DACM1 Owner's Manual And Installation Instructions page 19

Vertical heat/cool and heat pump models
Table of Contents

Advertisement

Installation Instructions
[] INSTALL THE DRAIN
An external
or an internal
chain
must
|xe attached
to
the ch"ain connector.
External
Drain
Attach a 90 ° PV(: elbow to tile unit's fbmale 3/4" NPI'
drain connectol: Lse the other end of the dbow to
1/111 a 3/4" Sch.40 PVC pipe through the knockout
holes ot both the wall plmmm and the archimctural
louver 1o the outside. Seal the gap between th_
plenum hole and PVC ulbe. S_e the Installation
Instructions
ill the l_\'_kI,l.
Inside wall
Side View
PVC
(External d rain}
90° Elbow
Internal Drain
Attach PVC to the tmit's ti:male
3/4" NPI" &-,tin
connectoc
Se( tim ]nsmllalioll
Inslluetions
ill tile
IL\VALI.
Local cod(s
may appl>:
inside wall
Side View
(Internaldrain}
[] DUCTWORK
Prepare
tile closet ductwork
{be later connection
to
the case.
The total flow role (CF*[) and exlernal static pres,,ure
(ESP) awilable can be esthnamd from tile chart below.
[ 7s*! t hese charts to select x_mr thn speed setting. Th_
,v
collar on top of th_ ca_ a(cepts standaM 10 duct.
Pull all duct tight. Extra duct slack can gl>atly increase
slatic pressur(.
CAUTION: Flex duct can collapse and cause airflow
re_tricfion_ Do not rtse flex duct for 90 ° bends or
unsupported
runs of 5 fL or more.
Airflow - CFM@230 Volts and @ 265 Volts
IndoorFanCFM
ESP
High
Medium Medium
Low
(in.water)
CFM
CFM
CFM
CFM
0.0
390
340
340
305
0.1
370
320
320
290
_-
0.2
350
300
300
270
0.3
330
280
280
250
'_
0.4
310
260
260
230
0.0
475
390
390
350
0.1
450
370
370
325
==
_-
0.2
425
350
350
300
0.3
400
330
330
275
'_
0.4
375
315
315
250
oo
0.0
630
545
545
490
0.1
610
530
530
480
==
0.2
590
515
515
470
0.3
570
495
495
455
'_
0.4
550
475
475
440
Tocorrectfor208 volts:O.91
Y*_ur airflow should
be balanc(d
based
on many
thctors, such as available
ESP, room
CFM, and
ductwork.
Consuh
all I l_:\C engineer
fi'w proper
applications.
External
static pressure
(ESP)
can be
measm-ed
with a manolneter
or pitot tube. Once
this
ESP is esta])lished,
}ou can calculate
tile CFM using
tile above chalt.
CFM Recommendations
• = Recommended M id Range
] tigher
CFMs
rand
to increas{
Sensible
capaci b,
enhallce
l-o(Nn cii-ct]lation
an(1 it]crease
duct
iloise,
while
lower
CFMs
tend
to increase
Latent
capacit}
and
rt duce
noise.
19