Start-Up - Water Wizard™ (optional)
L1
Function
Enter
Water Wizard™ User Interface
Key Function Description
1. Open the Solenoid
Confirm that the manual water supply valve
is closed. Press and hold the Function key
for one second. L3 will begin blinking (short on, long
off), indicating that Flow Test Mode is active and the
supply solenoid is open.
WARNING
Opening the manual supply valve will allow water
to pass to the media. Be sure the sump is safely
draining before opening the manual supply valve.
The manual supply valve ships closed and must be
adjusted for proper performance.
2. Set the Water Pressure
With the solenoid open, set the supply water
pressure to the correct setting from the
following tables. Use the manual supply valve to adjust
the supply pressure. A pressure gauge is provided
between the manual supply valve and the media.
The recommended water pressure for the model IGX
is set based on media width, model IG is set based
on air volume. A table is provided for each. Be sure
to refer to the correct table.
IGX
Media Width
Housing
(inches)
12
30
43¾
22
48
60
66
32
96*
*Multiple media sections. Value represents total media width.
Model IG
CFM Range
800 – 3500
3501 – 7000
3. Break-In Media
Leave the supply solenoid open to saturate and
break-in media for 20 minutes with the blower off.
34
Model IG / IGX Make-Up Air
L2
L3
Up
Down
NOTE
NOTE
Water Pressure
(in. wg)
20
36
42
61
72
42
Water Pressure
(in. wg)
50
74
4. Close Solenoid
With the pressure set, press the Function key
for one second to deactivate Flow Test Mode
and allow the supply solenoid to close.
5. Check Media
Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer
to Troubleshooting, Water Wizard™.
NOTE
Steps 6 through 8 are provided to adjust the
minimum cooling temperature. The minimum cooling
is preset to the factory recommended 75ºF (24ºC).
Only adjust if needed.
NOTE
The inlet air sensor function overrides and shuts
down the evaporative cooler if the outside
temperature falls below the minimum cooling
temperature.
6. Enter Program Mode
Press and hold
the Enter key
for three seconds. The
display will read "Pro"
when Program Mode is
active.
7. Adjust the Minimum Cooling
Temperature
While in the
Program Menu,
use the Up and
Down keys to
navigate the
Menu Options
until "toF" is
displayed. Press the
Enter key to access the selected Menu Option setting.
Use the Up and Down keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter key
to save the Minimum Cooling Temperature setting and
return to the Program Menu.
NOTE
The Enter key must be pressed to save the new
minimum cooling temperature.
8. Exit Program Mode
After ten seconds of idle time the controller will exit
Program Mode.