Maximum Output Voltage #2
Maximum Output Voltage #2
Program
Fundamental Parameters
Output Voltage #2
This parameter sets the maximum value of the output voltage of the ASD for
the #2 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Maximum Output Voltage #3
Program
Motor Settings
This parameter sets the maximum value of the output voltage of the ASD for
the #3 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.
Maximum Output Voltage #4
Program
Motor Settings
This parameter sets the maximum value of the output voltage of the ASD for
the #4 Motor Set.
Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.

Mode 1/2 Switching Frequency

Program
Frequency Settings
Switching Frequency
This parameter sets the threshold frequency that will be used in the Reference
Priority Selection parameter to determine if Frequency Mode #1 or #2 will
control the output of the ASD.

Motor 150% Time Limit

Program
Protection Settings
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
Thermal Protection setting for the #1 motor).
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
84
Fundamental #2
Max Output Voltage #3
Max Output Voltage #4
Reference Priority
Motor 150% Overload Time Limit
Maximum
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — (ASD dependent)
Units — Volts
Mode #1/#2
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Yes
Minimum — 0.10
Maximum — Max. Freq.
Units — Hz
Parameter Type — Numerical
Factory Default — 600
Changeable During Run — Yes
Minimum — 10
Maximum — 2400
Units — Seconds
W7 ASD Installation and Operation Manual