Carrier WEATHERMAKER 48J Started Manual page 62

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

ITEM
EC.EN
EC.MN
EC.MX
E.TRM
E. SEL
OA.E.C
OA.EN
OAT.L
O.DEW
ORH.S
E. TYP
EC.SW
E. CFG
E.P.GN
E.RNG
E.SPD
E.DBD
UEFC
FC.CF
FC. TM
FC.L.O
Table 79 -- Economizer Configuration Table
EXPANSION
Economizer
Installed?
Economizer
Min.Position
Economizer
Max.Position
Economzr Trim For SumZ ?
Econ ChangeOver
Select
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare
Value
High OAT Lockout Temp
OA Dewpoint Temp Limit
Outside Air RH Sensor
Economizer
Control Type
Economizer
Switch Config
ECON.OPERATION
CONFIGS
Economizer
Prop.Gain
Economizer
Range Adjust
Economizer
Speed Adjust
Economizer
Deadband
UNOCC.ECON.FREE
COOLING
Unoc Econ Free Cool Cfg
Unoc Econ Free Cool Time
Un.Ec.Free
Cool OAT Lock
RANGE
Yes/No
O- 100
O- 100
Yes/No
0-3
1-5
18 - 28
-40 - 120
50 - 62
Enable/Disable
1-3
0-2
0.7 - 3.0
0.5- 5
0.1 - 10
0.1 -2
0-2
0 - 720
40 - 70
%
%
I
d?
UNITS
CCN POINT
ECON
ENA
ECONOMIN
ECONOMAX
ECONTRIM
ECON
SEL
OAEC
SEL
OAEN
CFG
OAT LOCK
OAD-EWC FG
OARHSENS
ECON
CTL
ECOS_/CFG
EC PGAIN
EC RANGE
EC SPEED
EC DBAND
UEFC
CFG
UEFCTIME
UEFCNTLO
DEFAULT
Yes
5
98
Yes
0
4
24
60
55
Disable
g
1
2.5
0.75
0.5
o
12o
5o
Custom Psychrometric
Curves -- Refer to the psychrometric
chart and the standard Honeywell
A-D curves in Fig. 10. The
curves start from the bottom and rise vertically, angle to the left
and then fold over. This corresponds
to the limits imposed by
dry
bulb
changeover,
outdoor
enthalpy
changeover
and
outdoor
dewpoint
limiting
respectively.
Therefore,
it is now
possible to create any curve desired with the addition
of one
outdoor
relative
humidity
sensor
and
the
options
for
changeover
now available.
See Fig. 11 for an example
of a
custom curve constructed
on a psychrometric
chart.
UNOCCUPIED
ECONOMIZER
FREE
COOLING
-- This
Free Cooling function
is used to start the supply fan and use
the economizer
to bring
in outside
air when
the outside
temperature
is cool enough to pre-cool the space. This is done
to delay the need for mechanical
cooling
when the system
enters the occupied period. This function requires the use of a
space temperature
sensor.
When configured,
the economizer
will modulate
during an
unoccupied
period and attempt to maintain
space temperature
to the occupied cooling set point. Once the need for cooling has
been satisfied during this cycle, the fan will be stopped.
Configuring the economizer for Unoccupied Economizer
Free Cooling is done in the UEFC group. There are three
configuration options, FC CF, FC TM and FCLO.
Unoccupied
Economizer
Free
Cooling
Configuration
(F(2: CF) -- This option is used to configure the type of unoc-
cupied economizer free cooling control that is desired.
0 = disable unoccupied economizer free cooling
1 = perform unoccupied economizer free cooling as available
during the entire unoccupied period.
2 = perform unoccupied economizer free cooling as available,
FC TM minutes before the next occupied period.
Unoccupied Economizer Free Coolin_ Time Configuration
(FC TM) -- This option is a configurable time period, prior to
the next occupied period, that the control will allow unoccu-
pied economizer free cooling to operate. This option is only
applicable when FCCF = 2.
IC°,,"mC°;"t
Outside Enthalpy]
Changeover
I
default 24,0
J
De.point
default 55.0dF
[]
[]
Fig. 11 -- Custom Changeover Curve Example
62