Amana AAC081SRA Service Manual page 9

Slide out chassis room air conditioner
Hide thumbs Also See for AAC081SRA Service:
Table of Contents

Advertisement

Troubleshooting
information
WARNING
To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit and
discharge capacitor through a 10,000 ohm resistor before attempting to service, unless test procedures require
power to be connected. Ensure all ground wires are connected before certifying unit as repaired and/or
operational.
Corrective Action
Possible Causes
Overload protector open.
Rotary control faulty.
Wire(s) disconnected or loose.
Supply voltage out of specification.
Symptom
Compressor does not run,
fan motor operates normally.
Overload protector open.
Compressor cycles on and off.
Fan motor faulty.
Restricted air flow.
Compressor capacitor faulty.
Sealed refrigerant system fault.
Check protector for continuity.
If open, replace.
Ensure all control connections
are tight and secure. Check
control for proper operation
and installation. Replace if
faulty.
Ensure all connections are
tight and secure.
Check input voltage for proper
levels. Take appropriate
action if voltage levels out of
specification.
Check protector for continuity.
If open, replace.
Check fan motor for proper
operation. Replace if faulty.
Inspect air filter, indoor/
outdoor coil for dirt. Clean as
required. Check fins on coils
for damage. Straighten fins if
bent, attempt other repairs as
necessary. Replace coil if
repairs cannot be made.
Check capacitor for
short. Replace if faulty.
NOTE: Discharge capacitor
before testing.
Test sealed system for proper
charge, leaks, and restrictions.
@2003 Maytag Appliances
Company
16022061
Rev. 0
9