• Quick-Start guide
• PowerSure family user manual on CD (also
at www.liebert.com)
• Warranty card
• RJ-11 cord, 7 ft. (2.1 m)
• USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user
manual on CD.
Para una información más detallada, consulte
el manual del usuario de la familia PowerSure
en el CD.
I
NSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user
manual on the included CD or at
to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally
turned off. Place it in an area of unrestricted airflow around the unit, away from
water, flammable liquids, gases, corrosives and conductive contaminants. Maintain
a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an
ambient temperature range of 32°F to 104°F (0°C to 40°C).
2. Plug the PST's power cord into an AC outlet. Check the Site Wiring Fault Indicator
on the rear; if it is illuminated, refer to the Troubleshooting section.
3. Plug any computers and monitors into the orange receptacles for battery backup
and surge protection; other office machines that do not exceed the capacity of the
UPS may be plugged into either of the two (2) black receptacles, which provide
surge protection only.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).
6. Turn on connected equipment.
C
I
ONTROLS AND
NDICATORS
This button controls output power to
the connected load and has three
functions:
•Turns the PowerSure PST ON
•Turns the PowerSure PST OFF
•Silences PowerSure PST alarms
TURN THE UPS ON: Press and release the
main ON/OFF button to start the UPS. An
audible alarm will sound briefly.
TURN THE UPS OFF: When the PST is ON,
hold the main ON/OFF button down for more
than 2 seconds to shut it down. An audible
alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is
active, press and release the main ON/OFF
button to silence the audible alarm (Excep-
tions: low battery, overload and overtempera-
ture). DO NOT hold the button down for more
than 2 seconds or the PST will shut down.
CHECK THE PST'S CONDITION: Three sta-
tus indicators on the front of the UPS illumi-
nate to specify the status of the UPS (see
Troubleshooting section for details).
SITE WIRING FAULT INDICATOR (AMBER)
The Site
Wiring
Fault Indi-
cator on
the top of
thePST,
as shown,
illumi-
nates amber when the UPS detects a line-
neutral reversal or a poor neutral-ground.
(See Troubleshooting Chart if indicator is
illuminated.)
C
OMMUNICATIONS
The PowerSure PST has a USB interface port for communication that will work with the built-in Microsoft
Power Manager software on the user's PC, if the PC is so equipped. It will provide UPS status and man-
ages the automatic, orderly shutdown of the computer. The UPS (USB) communications meets HID stan-
dard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac
OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.
Quick-Start Guide for 350-500VA; 120V
B
HE
OX
Output receptacles
(battery backup and
surge protection)
www.liebert.com
before operating the UPS. Adhere
S
PECIFICATIONS
Model Number
Model Rating VA / W
DIMENSIONS: in (mm)
Unit W x D x H
Shipping W x D x H
WEIGHT: lbs (kg)
Unit
Shipping
INPUT AC PARAMETERS
Surge Protection
Voltage Range Without
Battery Operation
Frequency
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
Voltage (Battery Mode)
Output Current
Waveform (Battery Mode)
Frequency (Battery Mode)
Overload Warning
Overload Shutdown
BATTERY PARAMETERS
Top of UPS
Type
Quantity x Voltage x Rating 1 x 12V x 5 Ah
Site Wiring
Transfer Time
Fault
Indicator
(Amber)
Back-up Time:
Full load
Half load
Recharge Time
PowerSure
TOP OF UPS
Output receptacles
(surge protection
only)
Power ON/OFF/
Alarm Silence
Utility Indicator*
(Green)
Site Wiring Fault Indicator
(Red)
Fault Indicator* (Red/Green)
PA350-120U
350/225
6.6 x 9.8 x 3.7
(168 x 250 x 95)
9.4 x 13.8 x 5.6
(238 x 350 x 142)
11.7 (5.3)
12.1 (5.5)
98VAC - 140VAC ±3VAC
57 - 63 Hz (±0.4Hz)
6.5 ft.attached, w/ NEMA 5-15 P
(3) NEMA 5-15R (orange) battery
backup+surge protection
(2) NEMA 5-15R (black) surge
120VAC ±8%
2.9 A
Stepped Sinewave
Valve-regulated, nonspillable, lead
4 – 6 ms typical
At 77°F (25°C), resistive loading, w/
fully charged batteries:
5 minutes
16 minutes
12 hours to 90% capacity, after full
discharge into resistive load
PST
LEFT SIDE OF UPS
Refer to Bottom for
Cautionary Markings
Circuit
protector
USB port
Plug this type of equipment
into black receptacles ONLY
Inkjet
printers
Plug computers, monitors,
routers and cash registers into
orange receptacles
PA500-120U
ENVIRONMENTAL
500 / 300
Operating
Temperature
Storage
6.6 x 9.8 x 3.7
Temperature
(168 x 250 x 95)
Relative
9.4 x 13.8 x 5.6
Humidity
(238 x 350 x 142)
Operating
Elevation
13.5 (6.1)
13.9 (6.3)
Audible Noise
603J
AGENCY
Safety
Surge
ESD
protection
Susceptibility
4.2 A
Electrical Fast
Transient/Burst
60Hz ±1Hz
>100%
Emissions
>110%
Harmonics
Conducted
Immunity
acid
Flicker
1 x 12V x 7 Ah
Transportation
3 minutes
15 minutes
Power cord
6.5 ft. (2m)
Data Line
Protection
Connectors
RIGHT SIDE OF UPS
Scanners
Fax
machines
+32°F to + 104°F
(0°C to +40°C)
+5°F to + 122°F (-
15°C to +50°C)
0% to 95%, non-
condensing
Up to 10,000 ft.
(3000 m) at 86°F
(30°C) w/o
derating
< 40 dBA, at 1
meter
UL 1778, c-UL
Listed
ANSI C62.41,
Category A, Level
3, (IEEE 587,
Category A);
EN61000-4-5,
Level 3, Criteria A
EN61000-4-2,
Level 3, Criteria A
EN61000-4-3,
Level 2, Criteria A
EN61000-4-4,
Level 3, Criteria A
FCC Part 15,
Subpart B,
Class B
EN61000-3-2
EN61000-4-6
EN61000-3-3
ISTA Procedure
1A

Advertisement

loading

Summary of Contents for Emerson PowerSure 350-500VA

  • Page 1 ’ • Quick-Start guide • PowerSure family user manual on CD (also at www.liebert.com) • Warranty card • RJ-11 cord, 7 ft. (2.1 m) • USB cable, 6 ft. (1.8m) For more details, refer to the PowerSure user manual on CD. Para una información más detallada, consulte el manual del usuario de la familia PowerSure en el CD.
  • Page 2 ROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the PowerSure PST experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy. 1. The Fault indicator 2.

This manual is also suitable for:

Powersure pa500-120uPowersure pa350-120uLiebert powersure pst pa350-120ul liebert powersure pst pa500-120u