Table 11 Recommended Conduit And Cable Sizes-Module Bypass Input; Table 12 Recommended Conduit And Cable Sizes-Module Output; Table 13 Recommended Conduit And Cable Sizes-Load Output; Table 14 Recommended Conduit And Cable Sizes-Load Bank Output - Emerson NXL UPS Systems Installation Manual

Liebert nxl maintenance bypass cabinet 250-400kva, 60hz
Table of Contents

Advertisement

Table 11
Recommended conduit and cable sizes—Module Bypass Input
UPS
Rating
System Input Voltage (VAC)
Maint
kVA kW Rectifier Bypass
250 225
480
480
300 270
480
480
400 360
480
480
500 450
480
480
Table 12
Recommended conduit and cable sizes—Module Output
UPS
System
Rating
Input Voltage (VAC)
Maint
kVA kW Rectifier Bypass
250 225
480
480
300 270
480
480
400 360
480
480
500 450
480
480
Table 13
Recommended conduit and cable sizes—Load Output
UPS Rating
System Input Voltage (VAC)
kVA
kW
Rectifier Bypass
250
225
480
480
300
270
480
480
400
360
480
480
500
450
480
480
Table 14
Recommended conduit and cable sizes—Load Bank Output
UPS Rating
kVA
kW
250
225
300
270
400
360
500
450
Nominal Selection
Top Cable Entry
Wire & Conduit
Byp
Output
Ph, N, G,THW / FMC
(2) 3C 3-250kcmil,
480
480
2-250kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
480
480
2-350kcmil, #1/0AWG
(2) 4C 3-500kcmil,
480
480
2-500kcmil, #1/0AWG
(3) 3.5C 3-500kcmil,
480
480
2-250kcmil , #1/0AWG
Nominal Selection
Top Cable Entry
Wire & Conduit
Byp
Output
Ph, N, G THW / FMC
(2) 3C 3-250kcmil,
480
480
2-250kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
480
480
2-350kcmil, #1/0AWG
(2) 4C 3-500kcmil,
480
480
2-500kcmil, #1/0AWG
(3) 3.5C 3-500kcmil,
480
480
2-250kcmil , #1/0AWG
Nominal Selection
Top Cable Entry
Maint
Wire & Conduit
Byp
Output
Ph, N, G THW / FMC
(2) 3C 3-250kcmil,
480
480
2-250kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
480
480
2-350kcmil, #1/0AWG
(2) 4C 3-500kcmil,
480
480
2-500kcmil, #1/0AWG
(3) 3.5C 3-500kcmil,
480
480
2-250kcmil , #1/0AWG
System Input Voltage, VAC
Rectifier
Bypass
480
480
480
480
480
480
480
480
28
Module Bypass Input
Bottom Cable Entry
Top Cable Entry
Wire & Conduit
Wire & Conduit
Ph, N, G, THW / RNC
Ph, N, G, THW / FMC
(2) 3C 3-250kcmil,
(3) 2C 3-#2/0AWG,
2-250kcmil, #1/0AWG
2-#2/0AWG, #1/0AWG
(2) 3.5C 3-350kcmil,
(3) 3C 3-#4/0AWG,
2-350kcmil, #1/0AWG
2-#4/0AWG, #1/0AWG
(2) 4C 3-500kcmil,
(3) 3C 3-250kcmil,
2-500kcmil, #1/0AWG
2-250kcmil, #1/0AWG
(3) 4C 3-500kcmil,
(4) 3C 3-250kcmil,
2-250kcmil , #1/0AWG
2-#4/0AWG, #1/0AWG
Module Output
Bottom Cable Entry
Top Cable Entry
Wire & Conduit
Wire & Conduit
Ph, N, G THW / RNC
Ph, N, G THW / FMC
(2) 3C 3-250kcmil,
(3) 2C 3-#2/0AWG,
2-250kcmil, #1/0AWG
2-#2/0AWG, #1/0AWG
(2) 3.5C 3-350kcmil,
(3) 3C 3-#4/0AWG,
2-350kcmil, #1/0AWG
2-#4/0AWG, #1/0AWG
(2) 4C 3-500kcmil,
(3) 3C 3-250kcmil,
2-500kcmil, #1/0AWG
2-250kcmil, #1/0AWG
(3) 4C 3-500kcmil,
(4) 3C 3-250kcmil,
2-250kcmil , #1/0AWG
2-#4/0AWG, #1/0AWG
Load Output
Bottom Cable Entry
Top Cable Entry
Wire & Conduit
Wire & Conduit
Ph, N, G THW / FMC
Ph, N, G THW / FMC
(2) 3C 3-250kcmil,
(3) 2C 3-#2/0AWG,
2-250kcmil, #1/0AWG
2-#2/0AWG, #1/0AWG
(2) 3.5C 3-350kcmil,
(3) 3C 3-#4/0AWG,
2-350kcmil, #1/0AWG
2-#4/0AWG, #1/0AWG
(2) 4C 3-500kcmil,
(3) 3C 3-250kcmil,
2-500kcmil, #1/0AWG
2-250kcmil, #1/0AWG
(3) 4C 3-500kcmil,
(4) 3C 3-250kcmil,
2-250kcmil , #1/0AWG
2-#4/0AWG, #1/0AWG
Maint Byp
Output
480
480
480
480
480
480
480
480
Specifications
Alternate Selection
Bottom Cable Entry
Wire & Conduit
Ph, N, G THW / RNC
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Alternate Selection
Bottom Cable Entry
Wire & Conduit
Ph, N, G THW / RNC
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Alternate Selection
Bottom Cable Entry
Wire & Conduit
Ph, N, G THW / FMC
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Load Bank Output
Nominal Selection
Front Cable Entry
Wire-3W + GND
(1) 3-500kcmil, #1/0AWG
(2) 3-#4/0AWG, #1/0AWG
(2) 3-350kcmil, #1/0AWG
(2) 3-500kcmil, #1/0AWG

Advertisement